An effectiveness-NTU technique for characterising tube-in-tank phase change thermal energy storage systems

被引:168
作者
Tay, N. H. S. [1 ]
Belusko, M. [1 ]
Bruno, F. [1 ]
机构
[1] Univ S Australia, Barbara Hardy Inst, Mawson Lakes, SA 5095, Australia
关键词
Effectiveness-NTU; Thermal storage system; Phase change material; CARBON-FIBER BRUSHES; HEAT-TRANSFER; PART II; PERFORMANCE; SLURRY; PCM; SOLIDIFICATION; CAPSULES; FLOW;
D O I
10.1016/j.apenergy.2011.09.039
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Thermal storage systems with phase change materials are predominantly designed, analysed and optimised through numerical modelling. An alternative simplified method is being proposed for the characterisation of these phase change thermal storage systems. The method is based on the effectiveness-number of transfer units (E-NTUs) technique. A simplified mathematical representation has been analytically developed using the E-NTU technique for a cylindrical tank filled with phase change material (PCM), with heat transfer fluid flowing through tubes inside the tank. Experiments have been carried out on a cylindrical tank filled with PCM and with one, two and four coils of tubes to validate the technique. Experimental results for the systems with a high heat transfer area compare well with those calculated from the model. The results show that this technique can readily be used as a design tool for sizing and optimising a thermal storage unit with phase change materials. From this study, it may be concluded that the model based on the E-NTU technique can accurately predict the average heat exchange effectiveness of the thermal storage system with a high heat transfer surface area during charging and discharging. (C) 2011 Elsevier Ltd. All rights reserved.
引用
收藏
页码:309 / 319
页数:11
相关论文
共 39 条
[21]   Solidification of pcm inside a spherical capsule [J].
Ismail, KAR ;
Henríquez, JR .
ENERGY CONVERSION AND MANAGEMENT, 2000, 41 (02) :173-187
[22]   NUMERICAL-SIMULATION OF A SHELL-AND-TUBE LATENT-HEAT THERMAL-ENERGY STORAGE UNIT [J].
LACROIX, M .
SOLAR ENERGY, 1993, 50 (04) :357-367
[23]  
Lane GA., 2018, SOLAR HEAT STORAGE L
[24]   Application of effectiveness-NTU relationship to parallel flow microchannel heat exchangers subjected to external heat transfer [J].
Mathew, B. ;
Hegab, H. .
INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2010, 49 (01) :76-85
[25]  
MEHLING H, 2008, EUR C LISB PORT
[26]  
Mehling H, 2008, HEAT MASS TRANSF, P1
[27]   Heat transfer characteristics of thermal energy storage system using PCM capsules: A review [J].
Regin, A. Felix ;
Solanki, S. C. ;
Saini, J. S. .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2008, 12 (09) :2438-2458
[28]   Forced convection heat transfer in a slurry of phase change material in an agitated tank [J].
Royon, L ;
Guiffant, G ;
Perrot, P .
INTERNATIONAL COMMUNICATIONS IN HEAT AND MASS TRANSFER, 2000, 27 (08) :1057-1065
[29]   Recent advances in research on cold thermal energy storage [J].
Saito, A .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2002, 25 (02) :177-189
[30]   Thermal performance of palmitic acid as a phase change energy storage material [J].
Sari, A ;
Kaygusuz, K .
ENERGY CONVERSION AND MANAGEMENT, 2002, 43 (06) :863-876