Investigation of the dielectric recovery in synthetic air in a high voltage circuit breaker

被引:30
作者
Seeger, M [1 ]
Naidis, G
Steffens, A
Nordborg, H
Claessens, M
机构
[1] ABB Switzerland Ltd, Corp Res, CH-5405 Baden, Switzerland
[2] RAS, Inst High Temp, Moscow 127412, Russia
[3] Abb Switzerland Ltd, High Voltage Technol, Zurich, Switzerland
关键词
D O I
10.1088/0022-3727/38/11/020
中图分类号
O59 [应用物理学];
学科分类号
摘要
The dielectric recovery of an axially blown arc in an experimental set-up based on a conventional HV circuit breaker was investigated both experimentally and theoretically. As a quenching gas, synthetic air was used. The investigated time range was from 10 [mu s to 10 Ins after current zero (CZ). A fast rise in the dielectric strength during the first 100 mu s, followed by a plateau and further rise later was observed. The dependences on the breaking current and pressure were determined. The measured dielectric recovery during the first 100 mu s after CZ could be reproduced with good accuracy by computational fluid dynamics simulations. From that it could be deduced that the temperature decay in the axis does not depend sensitively on the pressure. The dielectric recovery during the first 100 mu s scales therefore mainly with the filling pressure. The plateau in the breakdown characteristic is due to a hot vapour layer from the still evaporating PTFE nozzle surface.
引用
收藏
页码:1795 / 1804
页数:10
相关论文
共 30 条
[1]   The ionization kinetics and electric field in the leader channel in long air gaps [J].
Aleksandrov, NL ;
Bazelyan, EM ;
Kochetov, IV ;
Dyatko, NA .
JOURNAL OF PHYSICS D-APPLIED PHYSICS, 1997, 30 (11) :1616-1624
[2]   Tests on the breakdown of air at elevated temperatures in non-uniform electric fields [J].
Allen, NL ;
Lam, DSK ;
Greaves, DA .
IEE PROCEEDINGS-SCIENCE MEASUREMENT AND TECHNOLOGY, 2000, 147 (06) :291-295
[3]  
[Anonymous], 2013, PLASMA KINETICS ATMO
[4]  
[Anonymous], [No title captured]
[5]   DIELECTRIC STRENGTH, BOILING-POINT AND TOXICITY OF GASES - DIFFERENT ASPECTS OF THE SAME BASIC MOLECULAR-PROPERTIES [J].
BRAND, KP .
IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1982, 17 (05) :451-456
[6]   Simulation of gas flow phenomena in high-voltage self-blast circuit breakers at heavy fault current interruption [J].
Claessens, M ;
vonStarck, R ;
Thiel, HG .
IEEE TRANSACTIONS ON PLASMA SCIENCE, 1997, 25 (05) :1001-1007
[7]  
CLAESSENS M, 1998, P ASME JSME M SAN DI
[8]   MEASUREMENTS OF DECAY OF ARC COLUMN METPERATURE FOLLOWING INTERRUPTION [J].
EDELS, H ;
HOLME, JC .
BRITISH JOURNAL OF APPLIED PHYSICS, 1966, 17 (12) :1595-&
[9]  
FRIND G, 1974, IEEE T POWER AP SYST, VPA93, P1675, DOI 10.1109/TPAS.1974.293900
[10]   SURFACE RECESSION RATE OF AN ABLATING POLYMER [J].
KEMP, NH .
AIAA JOURNAL, 1968, 6 (09) :1790-&