Evaluation of air infiltration in a hub airport terminal: On-site measurement and numerical simulation

被引:61
作者
Liu, Xiaochen [1 ]
Lin, Lin [1 ]
Liu, Xiaohua [1 ]
Zhang, Tao [1 ]
Rong, Xiangyang [2 ]
Yang, Ling [2 ]
Xiong, Dizhan [2 ]
机构
[1] Tsinghua Univ, Dept Bldg Sci, Beijing 100084, Peoples R China
[2] China Southwest Architectural Design & Res Inst, Chengdu 610041, Sichuan, Peoples R China
基金
中国国家自然科学基金;
关键词
Airport terminal; Large space; Air infiltration; On-site measurement; CFD simulation; COMFORT CONDITIONS; LARGE BUILDINGS; INDOOR; VENTILATION; MODEL; PREDICTIONS; ENVIRONMENT; VALIDATION; ATRIUM; FLOW;
D O I
10.1016/j.buildenv.2018.07.006
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Currently, many airport terminals are being newly built or retrofitted. They are often designed with large open spaces, and entrances are usually open due to the continuous flow of passengers, which results in severe air infiltration. This paper investigated air infiltration in a Chinese hub airport terminal during three typical seasons by on-site measurements and computational fluid dynamics (CFD) simulations. The air-velocity method with CFD simulation was acceptable for estimating air infiltration because of the relatively constant airflow driven dominantly by stack pressure in large spaces. However, the tracer gas method was found to be unsuitable due to small differences in concentration. The air change rate varied from 0.14 to 0.56 h(-1), in which the maximum value occurred in the winter daytime when space heating systems were in operation. Air infiltration caused 71% of the heat loss during the winter testing period, and 26% of the heat gain during summer. Furthermore, air infiltration in winter directly influenced thermal comfort in occupant zones (PMV = -2.58-0.55, with an average value of -1.2). Therefore, more attention should be focused on the research into air infiltration in large space buildings.
引用
收藏
页码:163 / 177
页数:15
相关论文
共 38 条
[1]   Energy Research in Airports: A Review [J].
Alba, Sergio Ortega ;
Manana, Mario .
ENERGIES, 2016, 9 (05)
[2]   Design analysis of single-sided natural ventilation [J].
Allocca, C ;
Chen, QY ;
Glicksman, LR .
ENERGY AND BUILDINGS, 2003, 35 (08) :785-795
[3]  
[Anonymous], 2010, E779 ASTM
[4]  
[Anonymous], 1980, Numerical heat transfer and fluid flow
[5]  
[Anonymous], 2015, THESIS
[6]  
ASTM, 2010, E741 ASTM
[7]   Energy conservation potential, HVAC installations and operational issues in Hellenic airports [J].
Balaras, CA ;
Dascalaki, E ;
Gaglia, A ;
Droutsa, K .
ENERGY AND BUILDINGS, 2003, 35 (11) :1105-1120
[8]   Mean age of air in a naturally ventilated office: Experimental data and simulations [J].
Buratti, C. ;
Mariani, R. ;
Moretti, E. .
ENERGY AND BUILDINGS, 2011, 43 (08) :2021-2027
[9]  
Dewalle D. R., 1980, WATER VAPOR MASS BAL, P1
[10]  
Fluent Inc, 2007, Airpak 3.0 User's Guide