Heat pump combined with single-stage or two-stage desiccant wheel system? A comparative study on different humidity requirement buildings

被引:19
作者
Tian, Shaochen [1 ,2 ]
Su, Xing [1 ,2 ]
Geng, Yining [1 ,2 ]
Li, He [1 ,2 ]
Liang, Yaowen [1 ]
Di, Yanqiang [3 ]
机构
[1] Tongji Univ, Sch Mech Engn, Shanghai, Peoples R China
[2] Tongji Univ, Minist Educ, Key Lab Performance Evolut & Control Engn Struct, Shanghai, Peoples R China
[3] China Acad Bldg Res, Beijing, Peoples R China
关键词
Desiccant wheel; Heat pump; Indoor relative humidity; Energy consumption; PERFORMANCE ANALYSIS; COOLING SYSTEM; AIR; TEMPERATURE; DEHUMIDIFICATION; OPTIMIZATION; HOT; SIMULATION;
D O I
10.1016/j.enconman.2022.115345
中图分类号
O414.1 [热力学];
学科分类号
摘要
Heat pump desiccant wheel hybrid systems can control indoor temperature and humidity for industrial and civil buildings. To clarify the boundary of heat pump combined single-stage desiccant wheel system and two-stage desiccant wheel system for judging the optimal system under different conditions, the performance of the two systems is analyzed with experiment and simulation method. Firstly, the fresh air process is compared for different humidity set points under typical operation conditions. Secondly, the energy moisture ratio (EMR) of desiccant wheels is analyzed. At last, based on system energy consumption and economy, the humidity boundary of the single-stage and the two-stage dehumidification system is proposed, under different conditions. It is found that the energy performance of desiccant wheel increases with the reducing of humidity set point for both systems, and higher EMR can be obtained by the desiccant wheel of the single-stage dehumidification system for all operation modes. The two-stage dehumidification system is more energy efficient when humidity for the controlled space is lower than 49%, 55% and 40% for high temperature mode, typical summer mode and typical dehumidification mode, separately. With the proposed operation boundary, the optimal system can be quickly judged according to the humidity control requirement and outdoor environment.
引用
收藏
页数:12
相关论文
共 50 条
[1]   Modelling and control optimization of a solar desiccant and evaporative cooling system using an electrical heat pump [J].
Aprile, Marcello ;
Scoccia, Rossano ;
Motta, Mario .
1ST INTERNATIONAL CONFERENCE ON SOLAR HEATING AND COOLING FOR BUILDINGS AND INDUSTRY (SHC 2012), 2012, 30 :478-489
[2]   Experimental investigations on thin polymer desiccant wheel performance [J].
Cao, Tao ;
Lee, Hoseong ;
Hwang, Yunho ;
Radermacher, Reinhard ;
Chun, Ho-Hwan .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2014, 44 :1-11
[3]   Silica gel/polymer composite desiccant wheel combined with heat pump for air-conditioning systems [J].
Chen, Chih-Hao ;
Hsu, Chien-Yeh ;
Chen, Chih-Chieh ;
Chiang, Yuan-Ching ;
Chen, Sih-Li .
ENERGY, 2016, 94 :87-99
[4]   Energy saving potential of a hybrid HVAC system with a desiccant wheel activated at low temperatures and an indirect evaporative cooler in handling air in buildings with high latent loads [J].
Comino, F. ;
Ruiz de Adana, M. ;
Peci, F. .
APPLIED THERMAL ENGINEERING, 2018, 131 :412-427
[5]   Experimental and numerical analysis of desiccant wheels activated at low temperatures [J].
Comino, F. ;
Ruiz de Adana, M. .
ENERGY AND BUILDINGS, 2016, 133 :529-540
[6]   Seasonal Variations of Indoor Microbial Exposures and Their Relation to Temperature, Relative Humidity, and Air Exchange Rate [J].
Frankel, Mika ;
Beko, Gabriel ;
Timm, Michael ;
Gustavsen, Sine ;
Hansen, Erik Wind ;
Madsen, Anne Mette .
APPLIED AND ENVIRONMENTAL MICROBIOLOGY, 2012, 78 (23) :8289-8297
[7]   Performance assessment and transient optimization of air precooling in multi-stage solid desiccant air conditioning systems [J].
Gadalla, Mohamed ;
Saghafifar, Mohammad .
ENERGY CONVERSION AND MANAGEMENT, 2016, 119 :187-202
[8]   Exergy analysis of dehumidification systems: A comparison between the condensing dehumidification and the desiccant wheel dehumidification [J].
Ge, Fenghua ;
Wang, Cong .
ENERGY CONVERSION AND MANAGEMENT, 2020, 224 (224)
[9]   Energy savings potential of a desiccant assisted hybrid air source heat pump system for residential building in hot summer and cold winter zone in China [J].
Ge, Fenghua ;
Guo, Xinglong ;
Hu, Zicheng ;
Chu, Yi .
ENERGY AND BUILDINGS, 2011, 43 (12) :3521-3527
[10]   Experimental investigation on a one-rotor two-stage rotary desiccant cooling system [J].
Ge, T. S. ;
Dai, Y. J. ;
Wang, R. Z. ;
Li, Y. .
ENERGY, 2008, 33 (12) :1807-1815