Diagnosing Shorted Turns on the Windings of Power Transformers Based Upon Online FRA Using Capacitive and Inductive Couplings

被引:117
作者
Behjat, Vahid [1 ]
Vahedi, Abolfazl [2 ]
Setayeshmehr, Alireza [1 ]
Borsi, Hossein [1 ]
Gockenbach, Ernst [1 ]
机构
[1] Leibniz Univ Hannover, Schering Inst, Inst Elect Power Syst, High Voltage Engn Sect, D-30167 Hannover, Germany
[2] Iran Univ Sci & Technol, Ctr Excellence Power Syst Automat & Operat, Tehran 16846, Iran
关键词
Interturn fault detection; online monitoring; power transformer; sweep frequency-response analysis; FREQUENCY-RESPONSE ANALYSIS; DISPLACEMENTS; DEFORMATION;
D O I
10.1109/TPWRD.2011.2151285
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Interturn faults are a significant problem in power transformers that can eventually burgeon into catastrophic faults and likely result in an overall network failure. The main problem with SFRA as one of the well-recognized diagnostic tools for detecting winding faults is its restriction to the domain of offline testing since the method requires injection of a test signal into the transformer windings through the high-voltage bushings. To address the difficulties arising from this issue, in this contribution, a new technique for online transfer function monitoring of the power transformers windings through a quite simple, economic, and noninvasive capacitive sensor installed on the surface of the transformer bushing is presented. Interturn faults with various levels of severity were imposed on the winding of a 35-kV/400-V, 100-kVA oil-immersed distribution transformer to evaluate the feasibility and sensitivity of the method. The experimental results proved that the newly developed online monitoring system is feasible and sensitive to detect unambiguously interturn faults even down to 0.2% shorted turns along the winding. As such, the proposed approach in this paper enables timely warning of a rising failure and serves a better purpose in assessing the health of a faulty transformer.
引用
收藏
页码:2123 / 2133
页数:11
相关论文
共 29 条
[1]  
[Anonymous], 2003, SWEEP FREQUENCY RESP
[2]  
[Anonymous], C571901 IEEE
[3]  
[Anonymous], C571900 IEEE
[4]  
Bartley W.H., 2003, P 36 ANN C INT ASS E
[5]  
Birlasekaran S., 1999, IEEE Power Engineering Review, V19, P54, DOI 10.1109/39.780991
[6]   Procedures for detecting winding displacements in power transformers by the transfer function method [J].
Christian, J ;
Feser, K .
IEEE TRANSACTIONS ON POWER DELIVERY, 2004, 19 (01) :214-220
[7]  
Christian J., 1999, P I EL ENG INT S HIG, P37
[8]  
Coffeen L., 2002, EPRI SUBST EQ DIAGN
[9]   TRANSFORMER DIAGNOSTIC TESTING BY FREQUENCY-RESPONSE ANALYSIS [J].
DICK, EP ;
ERVEN, CC .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1978, 97 (06) :2144-2153
[10]  
Florkowski M., 2004, I PHYS PUBLISH MEAS, V14, P1986