A novel adaptive distance protection scheme for DFIG wind farm collector lines

被引:44
作者
Ma, Jing [1 ,2 ]
Zhang, Weibo [1 ]
Liu, Jing [1 ]
Thorp, James S. [2 ]
机构
[1] North China Elect Power Univ, State Key Lab Alternate Elect Power Syst Renewabl, Beijing 102206, Peoples R China
[2] Virginia Polytech Inst & State Univ, Bradley Dept Elect & Comp Engn, Blacksburg, VA 24061 USA
关键词
Wind farm; Collector system; Adaptive distance protection; Fault resistance; RELAY; DESIGN; IMPACT;
D O I
10.1016/j.ijepes.2017.07.008
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In view of the sensitivity and selectivity problems in DFIG (doubly-fed induction generator) wind farm collector line protection, a new adaptive distance protection scheme is proposed. First, according to the geometric distribution characteristics of the collector line voltage and current, the equation of voltage drop from the relaying point to the fault point is established and the adaptive setting coefficient is calculated. On this basis, a new adaptive distance protection criterion is formed according to the phase relationship between the fault current and the measured current. Wind farm simulation tests on RTDS verify that, the proposed method is well adaptable to different operation modes, strongly immune to the fault resistance and unaffected by the weak feed characteristics of the wind generator collector system. (C) 2017 Elsevier Ltd. All rights reserved.
引用
收藏
页码:234 / 244
页数:11
相关论文
共 30 条
[1]  
Bin Wang, 2012, 11 INT C DPSP, P1
[2]  
Bo ZQ, 2016, PROT CONTR MOD POW, V1, DOI 10.1186/s41601-016-0012-2
[3]   Simultaneous impact of unified power flow controller and off-shore wind penetration on distance relay characteristics [J].
Dubey, Rahul ;
Samantaray, Subhransu Ranjan ;
Panigrahi, Bijay Ketan .
IET GENERATION TRANSMISSION & DISTRIBUTION, 2014, 8 (11) :1869-1880
[4]   Ground distance relay compensation based on fault resistance calculation [J].
Eissa, M. M. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2006, 21 (04) :1830-1835
[5]   A novel digital distance relaying technique for transmission line protection [J].
Eissa, MM ;
Masoud, M .
IEEE TRANSACTIONS ON POWER DELIVERY, 2001, 16 (03) :380-384
[6]  
Gonzalez-Longatt F., 2012, 11 IET INT C DPSP, P74
[7]  
Han Aoyang, 2010, 2010 International Conference on Modelling, Identification and Control (ICMIC), P71
[8]   Design and evaluation of a wind farm protection relay [J].
Haslam, SJ ;
Crossley, PA ;
Jenkins, N .
IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 1999, 146 (01) :37-44
[9]   Distance Protection of AC Grid With HVDC-Connected Offshore Wind Generators [J].
He, Lina ;
Liu, Chen-Ching ;
Pitto, Andrea ;
Cirio, Diego .
IEEE TRANSACTIONS ON POWER DELIVERY, 2014, 29 (02) :493-501
[10]   Distance Protection of Lines Emanating From Full-Scale Converter-Interfaced Renewable Energy Power Plants-Part I: Problem Statement [J].
Hooshyar, Ali ;
Azzouz, Maher A. ;
El-Saadany, Ehab F. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2015, 30 (04) :1770-1780