Retrofitting of R404a commercial refrigeration systems using R410a and R407f refrigerants

被引:30
作者
Bortolini, Marco [1 ]
Gamberi, Mauro [2 ]
Gamberini, Rita [3 ]
Graziani, Alessandro [1 ,2 ]
Lolli, Francesco [3 ]
Regattieri, Alberto [1 ]
机构
[1] Univ Bologna, Dept Ind Engn, I-40136 Bologna, Italy
[2] Univ Padua, Dept Management & Engn, I-36100 Vicenza, Italy
[3] Univ Modena & Reggio Emilia, Dept Sci & Methods Engn, I-42122 Reggio Emilia, Italy
关键词
Retrofitting; Stationary refrigeration system; Global warming potential; Hydrofluorocarbon; Experimental study; ALTERNATIVE REFRIGERANT; DROP-IN; PERFORMANCE; MIXTURE; REPLACEMENT; HCFC-22; PLANT; R134A; R22;
D O I
10.1016/j.ijrefrig.2015.02.015
中图分类号
O414.1 [热力学];
学科分类号
摘要
This paper presents an experimental analysis about the retrofitting of two commercial stationary refrigeration systems marketed by an Italian leading company. Such systems operate both at medium temperature (MT), i.e. [-5; 10]degrees C, and low temperature (LT), i.e. [-25; 15]degrees C, and they are originally designed to work with hydrofluorocarbon (HFC) R404a, known as a high global warming potential (GWP) fluid (GWP = 3922). The goal is to investigate the performances of HFC R410a (GWP = 2088) and R407f (GWP = 1825), chosen as effective alternatives to HFC R404a. Such fluids are compatible with the refrigeration systems, non-flammable and easy-available. Furthermore, they meet the European Union (EU) restrictions in force in the next future, so that they are suitable to start the transition toward efficient and eco-friendly refrigeration systems. The experimental campaign shows the feasibility of adopting R407f and R410a for the MT refrigeration system and R407f fluid for the system operating at LT. (C) 2015 Elsevier Ltd and IIR. All rights reserved.
引用
收藏
页码:142 / 152
页数:11
相关论文
共 29 条