Influence of temperature on phase shift angle and admittance of moistened composite of cellulose and insulating oil

被引:10
作者
Zukowski, Pawel [1 ]
Rogalski, Przemyslaw [1 ]
Koltunowicz, Tomasz N. [1 ]
Kierczynski, Konrad [1 ]
Subocz, Jan [2 ]
Sebok, Milan [3 ]
机构
[1] Lublin Univ Technol, Dept Elect Devices & High Voltage Technol, Lublin, Poland
[2] West Pomeranian Univ Technol, Dept Electrotechnol & Diagnost, Szczecin, Poland
[3] Univ Zilina, Dept Measurement & Applicat Elect Engn, Zilina, Slovakia
关键词
Precise measurements; Power transformer; Insulating oil; Electrotechnical pressboard; Moisture; Admittance; CHAIN-END GROUPS; DIELECTRIC RESPONSE; FREQUENCY-DOMAIN; IMPREGNATED PRESSBOARD; PAPER INSULATION; AC CONDUCTIVITY; MINERAL-OIL; WATER NANODROPS; NANOPARTICLES; TIME;
D O I
10.1016/j.measurement.2021.110041
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
This paper describes precise tests of frequency-temperature relations of the phase shift angle and admittance of a reference sample of composite of cellulose and insulating oil with a moisture content of (5.0 +/- 0.20)% by weight. A method of moisturisation the pressboard as close as possible to the natural moisturisation process in power transformers was used, which uses a moisture source from which moisture moves through the insulating oil to the reference sample. A climate chamber was used to ensure long-term temperature stabilisation, at uncertainties not exceeding +/- 0.01 K, for measuring the temperature dependence of alternating current parameters with high accuracy. A new method of determining the activation energy of relaxation time of the phase shift angle and admittance was developed, which allowed obtaining low uncertainty values of their determination. The values of activation energy of relaxation time of the phase shift angle Delta W-phi approximate to (0.914 +/- 0.0085) eV, activation energy of relaxation time of the admittance Delta W-tau Y approximate to(0.866 +/- 0.0023) eV, and activation energy of the admittance Delta W-Y approximate to (0.897 +/- 0.0043) eV were determined. Uncertainties of these parameters were +/- 0.93%, +/- 0.27% and +/- 0.48%, respectively.
引用
收藏
页数:13
相关论文
共 52 条
  • [1] [Anonymous], 1978, Physics,
  • [2] [Anonymous], 2008, EVALUATION MEASUREME
  • [3] Spectroscopic measurement and analysis of water and oil in transformer insulating paper
    Baird, PJ
    Herman, H
    Stevens, GC
    Jarman, PN
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2006, 13 (02) : 293 - 308
  • [4] Field experiences with measurements of dielectric response in frequency domain for power transformer diagnostics
    Blennow, J
    Ekanayake, C
    Walczak, K
    García, B
    Gubanski, SM
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2006, 21 (02) : 681 - 688
  • [5] Frequency response of oil impregnated pressboard and paper samples for estimating moisture in transformer insulation
    Ekanayake, Chandima
    Gubanski, Stanislaw M.
    Graczkowski, Andrzej
    Walczak, Krzysztof
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2006, 21 (03) : 1309 - 1317
  • [6] On the Frequency Domain Dielectric Response of Oil-paper Insulation at Low Temperatures
    Fofana, I.
    Hemmatjou, H.
    Meghnefi, F.
    Farzaneh, M.
    Setayeshmehr, A.
    Borsi, H.
    Gockenbach, E.
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2010, 17 (03) : 799 - 807
  • [7] Moisture in Cellulose Insulation of Power Transformers - Statistics
    Gielniak, J.
    Graczkowski, A.
    Moranda, H.
    Przybylek, P.
    Walczak, K.
    Nadolny, Z.
    Moscicka-Grzesiak, H.
    Feser, K.
    Gubanski, S. M.
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2013, 20 (03) : 982 - 987
  • [8] Kinetics of the production of chain-end groups and methanol from the depolymerization of cellulose during the ageing of paper/oil systems. Part 2: Thermally-upgraded insulating papers
    Gilbert, Roland
    Jalbert, Jocelyn
    Duchesne, Steve
    Tetreault, Pierre
    Morin, Brigitte
    Denos, Yves
    [J]. CELLULOSE, 2010, 17 (02) : 253 - 269
  • [9] Graczkowski A, 2010, PRZ ELEKTROTECHNICZN, V86, P223
  • [10] Detection of Power Transformer Bushing Faults and Oil Degradation using Frequency Response Analysis
    Hashemnia, Naser
    Abu-Siada, A.
    Islam, S.
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2016, 23 (01) : 222 - 229