Employing instantaneous positive sequence symmetrical components for voltage sag source relative location

被引:17
作者
Mohammadi, Younes [1 ]
Moradi, Mohammad H. [1 ]
Leborgne, Roberto Chouhy [2 ]
机构
[1] Bu Ali Sina Univ, Dept Elect Engn, Fac Engn, Hamadan, Iran
[2] Univ Fed Rio Grande do Sul, Porto Alegre, RS, Brazil
关键词
Power quality; Voltage sags; Source location; Instantaneous positive sequence; PROBABILISTIC ASSESSMENT; FINANCIAL LOSSES; INTERRUPTIONS; RELAY; POWER;
D O I
10.1016/j.epsr.2017.05.030
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Modern industrial facilities are vulnerable to voltage sags and short interruptions as they were in the past to sustainable interruptions. Therefore, modern reliability assessment should include voltage sags and short interruptions. Hence, in order to improve power system reliability it is necessary to mitigate these voltage variations. One of the first steps towards this objective is to locate the source of these disturbances. This paper investigates a number of methods for sag source relative location. Said methods are based on different electrical parameters. Using instantaneous positive sequence components, five novel extended methods for voltage sag source location are proposed for accommodating the transient nature of voltage sag events and for improving unsuitable operation of methods on asymmetrical sags and earth faults. Due to the fact that short circuits are the main reason resulting in voltage sags, this paper focuses on the location of voltage sag sources due to line faults. A comparative analysis between the existing methods and the five novel extended methods is performed by applying extensive numerical simulations in a Brazilian regional transmission and sub-transmission utility. Finally, the effectiveness of all methods is obtained. The results show that the novel extended methods are more effective and among them, the extended methods based on reactive power can locate sag sources with an accuracy of 88%. Also, implementation of the novel extended methods on signal processors is easier with respect to the already implemented methods. (C) 2017 Elsevier B.V. All rights reserved.
引用
收藏
页码:186 / 196
页数:11
相关论文
共 40 条
  • [1] [Anonymous], 2013, PRZEGLAD ELEKTOTECHN
  • [2] [Anonymous], INT C REN EN POW QUA
  • [3] Evaluation of fault relative location algorithms using voltage sag data collected at 25-kV substations
    Barrera Nunez, Victor
    Melendez Frigola, Joaquim
    Herraiz Jaramillo, Sergio
    Sanchez Losada, Jorge
    [J]. EUROPEAN TRANSACTIONS ON ELECTRICAL POWER, 2010, 20 (01): : 34 - 51
  • [4] Bollen M. H. J., 2000, IEEE PRESS SERIES PO
  • [5] Voltage sag prediction for network planning
    dos Santos, Andre
    Correia de Barros, M. T.
    [J]. ELECTRIC POWER SYSTEMS RESEARCH, 2016, 140 : 976 - 983
  • [6] Faisal MF, 2010, INT REV ELECTR ENG-I, V5, P2301
  • [7] Gomez J., 2005, 8 INT C EXH EL DISTR
  • [8] A new approach to locate the voltage sag source using real current component
    Hamzah, N
    Mohamed, A
    Hussain, A
    [J]. ELECTRIC POWER SYSTEMS RESEARCH, 2004, 72 (02) : 113 - 123
  • [9] Influence of voltage dips on industrial equipment: Analysis and assessment
    Honrubia-Escribano, A.
    Gomez-Lazaro, E.
    Molina-Garcia, A.
    Fuentes, J. A.
    [J]. INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2012, 41 (01) : 87 - 95
  • [10] Kanokbannakorn W., 2011, 8 INT C EL ENG EL CO