Reducing voltage sags through fault current limitation

被引:50
作者
Tosato, F [1 ]
Quaia, S [1 ]
机构
[1] Univ Trieste, Dept Elect Engn, DEEI, Trieste, Italy
关键词
fault current limitation; power quality; voltage sags;
D O I
10.1109/61.905572
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Short circuit current limitation in distribution utilities can be an effective way to improve power quality, since the expected voltage sag amplitude during faults can be dramatically reduced. A simple series LC circuit tuned at the net frequency, with the capacitor shunted by a metal oxide varistor (MOV), proves to be a well suited limiter to reach the goal. In the paper, the properties of such a circuit are analyzed and its operation is investigated through computer simulation. The relevant pro and con aspects are outlined and discussed.
引用
收藏
页码:12 / 17
页数:6
相关论文
共 50 条
  • [31] Voltage sags: Their impact on the utility and industrial customers
    Melhorn, CJ
    Davis, TD
    Beam, GE
    IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1998, 34 (03) : 549 - 558
  • [32] Uses of signal derivatives in analysis of voltage sags
    Hubbard, SJ
    Collins, ER
    2004 11TH INTERNATIONAL CONFERENCE ON HARMONICS AND QUALITY OF POWER, 2004, : 531 - 536
  • [33] SSC compensation capability of unbalanced voltage sags
    Fornari, F
    Procopio, R
    Bollen, MHJ
    IEEE TRANSACTIONS ON POWER DELIVERY, 2005, 20 (03) : 2030 - 2037
  • [34] Classification and Localization of Fault-Initiated Voltage Sags Using 3-D Polarization Ellipse Parameters
    Alam, Mollah Rezaul
    Muttaqi, K. M.
    Saha, Tapan Kumar
    IEEE TRANSACTIONS ON POWER DELIVERY, 2020, 35 (04) : 1812 - 1822
  • [35] Saturation in synchronous machines due to voltage sags
    Carlsson, F
    IEEE IEMDC'03: IEEE INTERNATIONAL ELECTRIC MACHINES AND DRIVES CONFERENCE, VOLS 1-3, 2003, : 1571 - 1575
  • [36] Induction Motor Interactions after Voltage Sags
    Wang, Zhijun
    Wang, Xiaoyu
    2013 IEEE ELECTRICAL POWER & ENERGY CONFERENCE (EPEC), 2013,
  • [37] Characterization of voltage sags in industrial distribution systems
    Yalcinkaya, G
    Bollen, MHJ
    Crossley, PA
    IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 1998, 34 (04) : 682 - 688
  • [38] Survey Regarding Additional Indicators for Voltage Sags
    Maier, Virgil
    Pavel, Sorin G.
    Beleiu, Horia G.
    Buda, Constantin
    2016 13TH INTERNATIONAL CONFERENCE ON DEVELOPMENT AND APPLICATION SYSTEMS (DAS 2016), 2016, : 103 - 107
  • [39] Improvement of power quality by means of fault current limitation
    Henry, S
    Baldwin, T
    PROCEEDINGS OF THE THIRTY-SIXTH SOUTHEASTERN SYMPOSIUM ON SYSTEM THEORY, 2004, : 280 - 284
  • [40] PRINCIPLES OF FAULT CURRENT LIMITATION BY A RESONANT LC CIRCUIT
    KARADY, GG