Experimental comparison of thermal conditions in office rooms: Diffuse ceiling ventilation, chilled beam system, and chilled ceiling combined with mixing ventilation

被引:8
|
作者
Lestinen, Sami [1 ]
Mustakallio, Panu [2 ]
Kilpelainen, Simo [1 ]
Kosonen, Risto [1 ,3 ]
Jokisalo, Juha [1 ]
Koskela, Hannu [4 ]
Melikov, Arsen Krikor [5 ]
机构
[1] Aalto Univ, Dept Mech Engn, Sahkomiehentie 4, Espoo 02150, Finland
[2] Halton Oy Ltd, Haltonintie 1-3, Kausala 47400, Finland
[3] Nanjing Tech Univ, Coll Urban Construct, Nanjing 210009, Peoples R China
[4] Turku Univ Appl Sci, Lemminkaisenkatu 14-18 B, Turku 20520, Finland
[5] Tech Univ Denmark, Int Ctr Indoor Environm & Energy, Nils Koppels Alle,Bldg 402, DK-2800 Lyngby, Denmark
关键词
RADIANT COOLING SYSTEMS; INDOOR AIR-QUALITY; PERSONALIZED VENTILATION; FLOW CHARACTERISTICS; NUMERICAL-ANALYSIS; OCCUPANT COMFORT; IMPROVING HEALTH; PERFORMANCE; ENVIRONMENT; TEMPERATURE;
D O I
10.1080/23744731.2019.1708210
中图分类号
O414.1 [热力学];
学科分类号
摘要
Thermal environments generated by diffuse ceiling ventilation (DCV), chilled beam (CB), and chilled ceiling with mixing ventilation (CCMV) systems were compared at different heat loads. Experiments were carried out in two test chambers, in which a double office layout was investigated near heated windows. The heat load strength was increased from a normal level of 37-40 W/floor-m(2) to a peak load level of 57-64 W/floor-m(2) to observe effects on indoor air thermal conditions and draft discomfort. The target indoor air temperature was 26 +/- 0.5 degrees C in the occupied zone. The results show that the air temperature, air speed, and draft rate levels were reasonable at a normal load and increased slightly at peak load conditions. The CCMV system provided the smallest share of locations in which the draft rate level was higher than 10%. None of the studied systems achieved the category A defined by EN ISO 7730. However, all the systems fulfilled the demands of category B, except for CB, which fell to category C at the peak load conditions by exceeding the draft rate limit in one location. Thermal conditions were at a similar level for the studied systems. However, CCMV may reduce slightly the draft discomfort.
引用
收藏
页码:631 / 642
页数:12
相关论文
共 50 条
  • [1] Thermal environment and air quality in office with personalized ventilation combined with chilled ceiling
    Lipczynska, Aleksandra
    Kaczmarczyk, Jan
    Melikov, Arsen K.
    BUILDING AND ENVIRONMENT, 2015, 92 : 603 - 614
  • [2] Indoor thermal environment in rooms with combined air conditioning system of displacement ventilation and chilled ceiling panel
    School of Muni. and Eviron. Eng., Xi'an Univ. of Arch. and Tech, Xi'an 710055, China
    Xi'an Jianzhu Keji Daxue Xuebao, 2007, 4 (558-562):
  • [3] A combined system of chilled ceiling, displacement ventilation and desiccant dehumidification
    Hao, Xiaoli
    Zhang, Guoqiang
    Chen, Youming
    Zou, Shenghua
    Moschandreas, Demetrios. J.
    BUILDING AND ENVIRONMENT, 2007, 42 (09) : 3298 - 3308
  • [4] Design Charts for Combined Chilled Ceiling Displacement Ventilation System
    Ghaddar, Nesreen
    Ghali, Kamel
    Saadeh, Ralph
    Keblawi, Amer
    ASHRAE TRANSACTIONS 2008, VOL 114, PT 2, 2008, 114 : 574 - +
  • [5] Comparison of chilled ceiling and mixing ventilation assisted by intermittent personalized ventilation: Thermal comfort and energy savings
    Al Assaad D.
    Ghali K.
    Ghaddar N.
    Renewable Energy and Power Quality Journal, 2020, 18 : 431 - 436
  • [6] Optimized selection and operation of the combined chilled ceiling system and displacement ventilation
    Ghaddar, N.
    Ghali, K.
    Saadeh, R.
    INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2010, 34 (15) : 1328 - 1340
  • [7] A nodal model for displacement ventilation and chilled ceiling systems in office spaces
    Rees, SJ
    Haves, P
    BUILDING AND ENVIRONMENT, 2001, 36 (06) : 753 - 762
  • [8] Simplified thermal model of spaces cooled with combined positive displacement ventilation and chilled ceiling system
    Ayoub, Mohamad
    Ghaddar, Nesreen
    Ghali, Kamel
    HVAC&R RESEARCH, 2006, 12 (04): : 1005 - 1030
  • [9] Impact of chilled ceiling on indoor air distribution in a room with mixing ventilation
    Wu, Xiaozhou
    Gao, Jie
    Lv, Pin
    Wang, Haichao
    Wang, Shugang
    Wang, Fenghao
    SCIENCE AND TECHNOLOGY FOR THE BUILT ENVIRONMENT, 2020, 26 (03) : 366 - 376
  • [10] NUMERICAL STUDY ON THERMAL INDOOR ENVIRONMENT OF AN OFFICE WITH HYBRID SYSTEM OF CHILLED CEILING PANEL AND DISPLACEMENT VENTILATION
    Zhao, Lei
    Feng, Yannan
    Yuan, Feng
    Zhang, Peidong
    ACRA 2009: PROCEEDINGS OF THE 4TH ASIAN CONFERENCE ON REFRIGERATION AND AIR-CONDITIONING, 2009, : 547 - 552