Experimental study of thermal breakdown products from halogenated extinguishing agents

被引:34
作者
Andersson, Berit [1 ]
Blomqvist, Per [2 ]
机构
[1] Lund Univ, Dept Fire Safety Engn & Syst Safety, SE-22100 Lund, Sweden
[2] SP Tech Res Inst Sweden, SE-50115 Boras, Sweden
关键词
Extinguishing agents; Thermal breakdown products; HF; COF(2); HFC; 125; Dodecafluoro-2; methylpentane-3-one; COMBUSTION; FLAMES; CF3H;
D O I
10.1016/j.firesaf.2010.11.004
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Thermal breakdown products from four different fire extinguishing agents have been analysed. The agents studied were: bromotrifluoromethane (Halon 1301), pentafluoroethane (HFC 125), heptafluoropropane (HFC 227ea) and dodecafluoro-2-methyl-pentane-3-one (C(6)F-ketone). In the tests, the studied agent was introduced into a propane flame in a diffusion flame burner. The combustion products were analysed using both conventional IR-techniques and FTIR. It could be concluded that for all four extinguishing agents that the extinguishing agent takes part in the combustion process resulting in production of CO and CO(2), which was also confirmed by the increase in smoke production with increasing amounts of agent introduced into the flame. Production of HF and COF(2) was found in experiments with all four extinguishing agents. In experiments with Halon 1301, the production of HBr was also determined. It was found that the main fraction of fluorine ends up as HF for HFC 227ea and HFC 125 at lower relative application rates. When approaching extinguishing concentrations, the fraction recovered as COF(2) increases, but the total recovery of fluorine, including HF and the remaining part of the fluorine, is found in various organic breakdown products. The recovery of fluorine as HF and COF(2) for the C(6)F-ketone is lower compared to HFC 227ea and HFC 125. There is a clear difference in the recovery of fluorine for Halon 1301 where an almost quantitative recovery as HF or COF(2) is found. Halon 1301 additionally contains bromine, which, to a large extent, is recovered as HBr. (C) 2010 Elsevier Ltd. All rights reserved.
引用
收藏
页码:104 / 115
页数:12
相关论文
共 30 条
[21]  
National Fire Protection Association (NFPA), 2001, STAND CLEAN AG FIR E
[22]  
*NIST, 2006, 69 NIST
[23]   A FLAT FLAME BURNER AS CALIBRATION SOURCE FOR COMBUSTION RESEARCH - TEMPERATURES AND SPECIES CONCENTRATIONS OF PREMIXED H-2/AIR FLAMES [J].
PRUCKER, S ;
MEIER, W ;
STRICKER, W .
REVIEW OF SCIENTIFIC INSTRUMENTS, 1994, 65 (09) :2908-2911
[24]  
Purser D.A., 1995, SFPE HDB FIRE PROTEC, V2nd
[25]  
RIVERS PE, 2001, P HAL OPT TECHN WORK, P341
[26]  
SASO Y, 1993, FIRE TECHNOL, V29, P22
[27]   The influence of fluorinated hydrocarbons on the combustion of gaseous mixtures in a closed vessel [J].
Shebeko, YN ;
Azatyan, VV ;
Bolodian, IA ;
Navzenya, VY ;
Kopyov, SN ;
Shebeko, DY ;
Zamishevski, ED .
COMBUSTION AND FLAME, 2000, 121 (03) :542-547
[28]  
Su J.Z., 1996, J. Fire Prot. Eng., V8, P45, DOI [10.1177/104239159600800201, DOI 10.1177/104239159600800201]
[29]  
2007, SAFETY DATA SHEET KI
[30]  