An experimental study on the operating performance of a novel reverse-cycle hot gas defrosting method for air source heat pumps

被引:104
作者
Hu Wenju [2 ]
Jiang Yiqiang [2 ]
Qu Minglu [1 ]
Ni Long [2 ]
Yao Yang [2 ]
Deng Shiming [1 ]
机构
[1] Hong Kong Polytech Univ, Dept Bldg Serv Engn, Kowloon, Hong Kong, Peoples R China
[2] Harbin Inst Technol, Inst Heat Pump & Air Conditioning Technol, Harbin 150090, Peoples R China
关键词
Air source heat pumps; Defrosting; Thermal energy storage (TES); Phase change material (PCM); Reverse-cycle hot gas;
D O I
10.1016/j.applthermaleng.2010.09.024
中图分类号
O414.1 [热力学];
学科分类号
摘要
This paper reports on an experimental study on the operating performance for a novel reverse-cycle hot gas defrosting method for air source heat pumps (ASHPs). Firstly, a description of both an experimental prototype ASHP unit where the novel reverse-cycle hot gas defrosting method may be realized, and its operating modes are presented. This is followed by reporting an experimental set up for testing the defrosting performance of the prototype ASHP unit using the novel thermal energy storage (TES) based reverse-cycle hot gas defrosting method. Finally, experimental results are presented and discussed. The experimental results suggested that the use of the novel reverse-cycle hot gas defrosting method for the experimental ASHP unit was able to help shorten the defrosting time by similar to 3 min or 38%, and minimize the risk of shutting down the ASHP unit due to low suction pressure through increasing the compressor's suction pressure by about 200 kPa, when compared to the use of the traditional standard reverse-cycle hot gas defrosting method. In addition, when the TES based reverse-cycle hot gas defrosting method was used, the mean indoor coil surface temperature during defrosting was about 25 K higher than that when the traditional standard reverse-cycle hot gas defrosting method was used. These results suggested that as compared to the use of the traditional standard reverse-cycle hot gas defrosting method, the use of the novel TES based defrosting method would enable a quicker space heating resumption, impacting less on indoor thermal environment due to defrosting. Hence, the novel TES based defrosting method was proven to be effective in reducing the current problems in ASHPs using standard reverse-cycle hot gas defrosting method, such as a longer defrosting time and a poor system reliability. (C) 2010 Elsevier Ltd. All rights reserved.
引用
收藏
页码:363 / 369
页数:7
相关论文
共 15 条
  • [1] The application of photo-coupler for frost detecting in an air-source heat pump
    Byun, JS
    Jeon, CD
    Jung, JH
    Lee, J
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2006, 29 (02): : 191 - 198
  • [2] Experiment investigation of reverse cycle defrosting methods on air source heat pump with TXV as the throttle regulator
    Ding, YJ
    Ma, GY
    Chai, QH
    Yi, JA
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2004, 27 (06): : 671 - 678
  • [3] Defrost cycle performance for a circular shape evaporator air source heat pump
    Hewitt, Neil
    Huang, Ming Jun
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2008, 31 (03): : 444 - 452
  • [4] Effects of fan-starting methods on the reverse-cycle defrost performance of an air-to-water heat pump
    Huang, D
    Yuan, XL
    Zhang, XQ
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2004, 27 (08): : 869 - 875
  • [5] Applying grey forecasting to predicting the operating energy performance of air cooled water chillers
    Jiang, YQ
    Yao, Y
    Deng, SM
    Ma, ZL
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2004, 27 (04): : 385 - 392
  • [6] KIMURA H, 1984, SOL ENERGY, V3, P9
  • [7] KRAKOW KI, 1993, ASHRAE TRAN, V99, P317
  • [8] Dynamic simulation of air-source heat pump during hot-gas defrost
    Liu, ZQ
    Tang, GF
    Zhao, FY
    [J]. APPLIED THERMAL ENGINEERING, 2003, 23 (06) : 675 - 685
  • [9] *NAT STAND PEOPL R, GB500192003 NAT STAN
  • [10] Heat pumps - status and trends in Asia and the Pacific
    Nishimura, T
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2002, 25 (04): : 405 - 413