A steady-state empirical model for evaluating energy efficient performance of centrifugal water chillers

被引:18
作者
Wang, Handong [1 ]
机构
[1] M&E Sch Shenzhen Polytech, Shenzhen 518055, Guangdong, Peoples R China
关键词
Centrifugal chiller; Coefficient of performance; Empirical model; Steady state; Parallel chillers; COMPRESSION LIQUID CHILLERS; POWER-CONSUMPTION; REFRIGERATION SYSTEM; GENETIC ALGORITHM; NEURAL-NETWORKS; FAULT-DETECTION; FLOW RATE; OPTIMIZATION; VALIDATION; SIMULATION;
D O I
10.1016/j.enbuild.2017.08.072
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
A multivariate polynomial empirical model for evaluating the coefficient of performance (COP) of centrifugal chillers was proposed in this work. The model variables are common parameters (i.e. pressures and temperatures) on chilled water side in chiller systems. It is independent of the cooling load or partial load ratio (PLR) required by most of empirical chiller models so that it can provide a new method to evaluate the COP of a chiller without measuring the chilled water flow rate which is anyway difficult to measure directly and accurately in many on-field operating chiller plants. This makes it easy and convenient to use for on-field engineers. On-field measurement and analysis indicate that the accuracy of the proposed model is near to the compared three empirical models quoted from literatures-Gordon-Ng universal (GNU) model, Bi-quadratic regression (BQ) model, and Multivariate polynomial regression (MP) model when internal data is considered. When external data is adopted, the proposed model is obviously superior to the other three models. When internal data is used, values of the coefficient of variation of root-mean-square error (CV) of the novel model for chillers 1-3# are respectively 2.985%, 4.295%, and 2.956% with the corresponding mean relative error (MRE) values varying from 2.14% to 3.41%. While external data is adopted, the CV values of the novel model for chillers 1-3# are respectively 5.13%, 8.84%, and 4.33% with the corresponding MRE values varying from 3.19% to 6.84%. The result is acceptable for engineering applications such as building energy audit, energy conservation management, and operation management of multi parallel centrifugal chillers. (C) 2017 Elsevier B.V. All rights reserved.
引用
收藏
页码:415 / 429
页数:15
相关论文
共 46 条
  • [1] Using two improved particle swarm optimization variants for optimization of daily electrical power consumption in multi-chiller systems
    Askarzadeh, Alireza
    Coelho, Leandro dos Santos
    [J]. APPLIED THERMAL ENGINEERING, 2015, 89 : 640 - 646
  • [2] Development, validation, and assessment of a high fidelity chilled water plant model
    Baillie, Brian P.
    Bollas, George M.
    [J]. APPLIED THERMAL ENGINEERING, 2017, 111 : 477 - 488
  • [3] A PSO-based algorithm for optimal multiple chiller systems operation
    Beghi, Alessandro
    Cecchinato, Luca
    Cosi, Giovanni
    Rampazzo, Mirco
    [J]. APPLIED THERMAL ENGINEERING, 2012, 32 : 31 - 40
  • [4] A steady-state model for the design and optimization of a centralized cooling system
    Beitelmal, Abdlmonem H.
    Patel, Chandrakant D.
    [J]. INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2010, 34 (14) : 1239 - 1248
  • [5] CONVENTIONAL CHILLER PERFORMANCES SIMULATION AND FIELD DATA
    BEYENE, A
    GUVEN, H
    JAWDAT, Z
    LOWREY, P
    [J]. INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 1994, 18 (03) : 391 - 399
  • [6] Transient simulation of vapour-compression packaged liquid chillers
    Browne, MW
    Bansal, PK
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2002, 25 (05): : 597 - 610
  • [7] Steady-state model of centrifugal liquid chillers
    Browne, MW
    Bansal, PK
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 1998, 21 (05): : 343 - 358
  • [8] A simplified method to evaluate the seasonal energy performance of water chillers
    Cecchinato, Luca
    Chiarello, Manuel
    Corradi, Marco
    [J]. INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2010, 49 (09) : 1776 - 1786
  • [9] Chan T.S., 2009, INT J COMPUT ELECT A, V3, P1303
  • [10] Chang Y.C., 2013, INT J ELECT COMMUN E, V3, P1