Corrosion and Deposits in Water-Cooled Generator Stator Windings: Part 4: Operating Experience with Flow Restrictions in Stator Cooling Water Systems

被引:0
作者
Svoboda, Matthias [1 ]
Bauer, Thomas [1 ]
机构
[1] SvoBaTech AG, Lauriedstr 7, CH-6300 Zug, Switzerland
来源
POWERPLANT CHEMISTRY | 2019年 / 21卷 / 02期
关键词
D O I
暂无
中图分类号
O69 [应用化学];
学科分类号
081704 ;
摘要
A common problem with water-cooled generator stator windings is plugging of the hollow conductors that act as cooling channels. The causes are sometimes difficult to identify, but some common factors can be found. Insufficient layup during outages is a common one. The importance of good monitoring and maintenance practices is highlighted throughout the discussed examples. The stator is the main concern, because of its vulnerability to oxide deposits in the hollow conductors and the fact that if it fails, the whole power plant has to be shut down. Strainers and filters can also plug up and act as early warning devices for stator plugging. If replacing them is not an option, chemical cleaning can help, but it usually only removes the symptoms. Proactive treatment of these problems should be a priority, as damages can go into the millions. Even when cleaning is still possible, persistent deposits can often only be removed by more invasive treatments.
引用
收藏
页码:62 / 72
页数:11
相关论文
共 9 条
[1]  
Bauer T., 2014, PowerPlant Chem., V16, P94
[2]  
Bauer T., 2019, PowerPlant Chem., V21
[3]  
Farley S., 2002, SIEMENS STATOR WATER
[4]  
Guide on Stator Water Chemistry Management, 2011, A115 CIGRE
[5]   Quantitative in vitro comparison of the thrombogenicity of commercial dental implants [J].
Milleret, Vincent ;
Lienemann, Philipp S. ;
Bauer, Sebastian ;
Ehrbar, Martin .
CLINICAL IMPLANT DENTISTRY AND RELATED RESEARCH, 2019, 21 :8-14
[6]  
Ricker S., 2011, CHEM CLEANING GENERA
[7]  
Svoboda R, 2018, POWERPLANT CHEM, V20, P290
[8]  
Svoboda R, 2018, POWERPLANT CHEM, V20, P297
[9]  
Svoboda R, 2018, POWERPLANT CHEM, V20, P326