A Monitoring Equipment Charging System for HVTL Based on Domino-Resonator WPT With Constant Current or Constant Voltage Output

被引:48
作者
Yan, Zhaotian [1 ]
Xie, Huaqiang [1 ]
Li, Yong [1 ]
He, Zhengyou [1 ]
Yang, Huanyu [1 ]
Zhou, Wei [1 ]
Zhu, Chenyan [1 ]
Jing, Xiao [1 ]
Chen, Shaonan [1 ]
Mai, Ruikun [1 ]
机构
[1] Southwest Jiaotong Univ, Sch Elect Engn, Chengdu 611756, Peoples R China
基金
中国国家自然科学基金;
关键词
Coils; Monitoring; Voltage; Insulators; Current transformers; High-voltage techniques; Batteries; Constant current (CC); constant voltage (CV); domino-resonator; high voltage transmission line (HVTL); monitoring equipment charging; wireless power transfer (WPT); WIRELESS POWER TRANSFER; DESIGN; OPTIMIZATION; OVERHEAD;
D O I
10.1109/TPEL.2021.3123506
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The domino-resonator wireless power transfer system is designed in this work to harvest energy from the magnetic field around a 110-kV high voltage transmission line and supply power to the online monitoring device continuously over 1.1 meters insulation distance. Each domino resonator is evenly spaced and is embedded inside sealed insulation discs. The theoretical analysis shows that the constant voltage (CV) mode and the constant current (CC) mode can be realized by adjusting the receiver's switch state, which can meet the battery's CV and CC charging requirements. Such a method cancels the communication between the transmitter and the receiver. The finite-element simulation results show that the influence on the electric and magnetic field intensity distribution near the insulator can be negligible. Finally, a 30 W prototype with an output voltage of 7 V is built. The experimental results show that the fluctuation of output voltage (CV mode) and output current (CC mode) is less than 6% and 7%, respectively. The maximum efficiency is higher than 40% when the transmission distance is 1.1 m, and the number of coils is 12.
引用
收藏
页码:3668 / 3680
页数:13
相关论文
共 40 条
[1]  
[Anonymous], 2010, POWER SYST CLEAN ENE
[2]  
Auvigne C, 2012, 2012 XXTH INTERNATIONAL CONFERENCE ON ELECTRICAL MACHINES (ICEM), P2287, DOI 10.1109/ICElMach.2012.6350201
[3]   Resonant Wireless Charging System Design for 110-kV High-Voltage Transmission Line Monitoring Equipment [J].
Cai, Changsong ;
Wang, Junhua ;
Liu, Rong ;
Fang, Zhijian ;
Zhang, Pengcheng ;
Long, Mengjiao ;
Hu, Meilin ;
Lin, Zhongzheng .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2019, 66 (05) :4118-4129
[4]   A Novel Power Supply of Online Monitoring Systems for Power Transmission Lines [J].
Du, Lin ;
Wang, Caisheng ;
Li, Xianzhi ;
Yang, Lijun ;
Mi, Yan ;
Sun, Caixin .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2010, 57 (08) :2889-2895
[5]   Research on Wireless Network-based Power Line Inspection [J].
Han Kai ;
Xu Hongrui .
2009 INTERNATIONAL FORUM ON INFORMATION TECHNOLOGY AND APPLICATIONS, VOL 1, PROCEEDINGS, 2009, :379-+
[6]   Magnetic Field Energy Harvesting from AC Lines for Powering Wireless Sensor Nodes in Smart Grids [J].
Hosseinimehr, Tahoura ;
Tabesh, Ahmadreza .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2016, 63 (08) :4947-4954
[7]  
Huang XB, 2012, PROCEEDINGS OF 2012 IEEE INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS (IEEE CMD 2012), P581, DOI 10.1109/CMD.2012.6416211
[8]   Maximizing Air Gap and Efficiency of Magnetic Resonant Coupling for Wireless Power Transfer Using Equivalent Circuit and Neumann Formula [J].
Imura, Takehiro ;
Hori, Yoichi .
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2011, 58 (10) :4746-4752
[9]   Battery, Ultracapacitor, Fuel Cell, and Hybrid Energy Storage Systems for Electric, Hybrid Electric, Fuel Cell, and Plug-In Hybrid Electric Vehicles: State of the Art [J].
Khaligh, Alireza ;
Li, Zhihao .
IEEE TRANSACTIONS ON VEHICULAR TECHNOLOGY, 2010, 59 (06) :2806-2814
[10]   Wireless power transfer via strongly coupled magnetic resonances [J].
Kurs, Andre ;
Karalis, Aristeidis ;
Moffatt, Robert ;
Joannopoulos, J. D. ;
Fisher, Peter ;
Soljacic, Marin .
SCIENCE, 2007, 317 (5834) :83-86