Validation of a passive flux sampler for on-site measurement of formaldehyde emission rates from building and furnishing materials

被引:15
作者
Blondel, Alodie [1 ,2 ]
Plaisance, Herve [1 ,2 ]
机构
[1] Univ Lille Nord France, F-59000 Lille, France
[2] Ecole Mines Douai, Dept Chim & Environm, F-59508 Douai, France
关键词
CARBONYL-COMPOUNDS; INDOOR AIR; FIELD;
D O I
10.1039/c0ay00416b
中图分类号
O65 [分析化学];
学科分类号
070302 ; 081704 ;
摘要
A diffusive sampling device was developed for screening indoor sources of formaldehyde and determining the emission rates of these sources on-site. It consists of a glass Petri dish containing a quartz filter coated with 2,4-dinitrophenylhydrazine (DNPH) which is placed on the tested material for sampling. Formaldehyde emitted from the material diffuses through the air column inside the sampler and is collected onto the DNPH filter. The formaldehyde emission rate is determined from the mass collected by the sampler. The dependence of the sampled formaldehyde amount on the diffusion length inside the sampler was examined and led us to select a length of 20 mm for which the diffusion in the air layer controls the mass transfer from the material to the sampling surface (filter). A linear relationship with a high correlation (r(2) = 0.97) was obtained between the mass collected by the passive flux sampler and the emission rates measured by a standard chamber method, analysing a large series of indoor materials with the two methods in parallel. Neither the sampling time (ranging from 4 to 8 h) nor the temperature (from 23 to 35 degrees C) was observed to influence the sampler performance. Furthermore, the detection limit attained 1.2 mu g m(-2) h(-1) for a 6h-sampling time and a satisfying precision of replicate measurements (relative standard deviation of 7.8% on average) is adequate for monitoring the emission rates of primary sources contributing to formaldehyde indoor concentrations.
引用
收藏
页码:2032 / 2038
页数:7
相关论文
共 19 条
  • [1] *AFSSET, 2007, VAL GUID QUAL AIR IN, P78
  • [2] [Anonymous], 2006, EN ISO 16000-9
  • [3] [Anonymous], 2007, IARC MONOGRAPHS
  • [4] [Anonymous], 2006, 1600010 ISO
  • [5] Characterization and reduction of formaldehyde emissions from a low-VOC latex paint
    Chang, JCS
    Guo, ZS
    Fortmann, R
    Lao, HC
    [J]. INDOOR AIR, 2002, 12 (01) : 10 - 16
  • [6] GRIMALDI F, 1996, POLLUT ATMOS, V149, P330
  • [7] Sources of formaldehyde, other aldehydes and terpenes in a new manufactured house
    Hodgson, AT
    Beal, D
    McIlvaine, JER
    [J]. INDOOR AIR, 2002, 12 (04) : 235 - 242
  • [8] Secondary VOC emissions from flooring material surfaces exposed to ozone or UV irradiation
    Kagi, N.
    Fujii, S.
    Tamura, H.
    Namiki, N.
    [J]. BUILDING AND ENVIRONMENT, 2009, 44 (06) : 1199 - 1205
  • [9] Emission rates of formaldehyde from materials and consumer products found in California homes
    Kelly, TJ
    Smith, DL
    Satola, J
    [J]. ENVIRONMENTAL SCIENCE & TECHNOLOGY, 1999, 33 (01) : 81 - 88
  • [10] Characterization of curing emissions from conversion varnishes
    McCrillis, RC
    Howard, EM
    Guo, ZS
    Krebs, KA
    Fortmann, R
    Lao, HC
    [J]. JOURNAL OF THE AIR & WASTE MANAGEMENT ASSOCIATION, 1999, 49 (01) : 70 - 75