District Heating Safety Issues: Interactions Between Grounding Systems and Thermal Installations

被引:3
作者
Abdin, Giulio Cerino [1 ]
Freschi, Fabio [1 ]
Mitolo, Massimo [2 ]
Poggio, Alberto [1 ]
Tartaglia, Michele [1 ]
机构
[1] Politecn Torino, Dept Energy, I-10129 Turin, Italy
[2] Engn Syst Inc, Foothill Ranch, CA 92610 USA
关键词
Combined heat and power; district heating; electrical safety; grounding; insulating joints;
D O I
10.1109/TIA.2015.2511088
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
The structure of a district heating network lends itself to interactions among the grounding system of the generating plant, and those of the users, with the possibility that hazardous-induced voltages may occur on the latter. Hazards are possible due to the bonding of the heating system pipes to customer's grounding systems, as well as to possible high values of fault currents. These electrical safety issues due to grounding electrode interactions have been so far poorly treated in technical literature. District heating pipes are generally dielectrically separated in segments by means of insulating joints. A deeper analysis of such joints shows that the hot water circulating in the pipes may bypass their insulation, rendering the effectiveness of the dielectric separation strongly dependent on the joint geometry, and on the water electrical conductivity. The authors propose possible schemes for the hot water pipe connections, and discuss their efficiency based upon the electrical configuration of the generation plant. An experimental verification procedure to assess the electrical safety of the district heating system is also proposed.
引用
收藏
页码:2040 / 2045
页数:6
相关论文
共 13 条
[1]  
[Anonymous], 2013, QUAL TRANSM SERV MIN
[2]  
[Anonymous], 2013, MED VOLT SHORT CIRC
[3]  
[Anonymous], 2012, 505222010 EN
[4]  
[Anonymous], 2007, 604791 IECTS
[5]  
[Anonymous], 2000, IEEE Std 80-2000
[6]  
[Anonymous], 2002, 60364554 IEC
[7]   Insulated joint for corrosion protection of buried subway gallery structure: Consideration on cable ground connection [J].
Canova, A ;
Gruosso, G ;
Tartaglia, M .
IEEE TRANSACTIONS ON POWER DELIVERY, 2006, 21 (02) :966-970
[8]  
Euroheat & Power, 2008, GUID DISTR HEAT SUBS
[9]   Interferences Phenomena Between Separate Grounding Systems [J].
Freschi, Fabio ;
Mitolo, Massimo ;
Tartaglia, Michele .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2014, 50 (04) :2853-2860
[10]  
*IEC, 2005, 60364441 IEC