An improved model for predicting performance of finned tube heat exchanger under frosting condition, with frost thickness variation along fin

被引:65
作者
Tso, CP [1 ]
Cheng, YC
Lai, ACK
机构
[1] Multimedia Univ, Fac Engn & Technol, Melaka 75450, Malaysia
[2] Nanyang Technol Univ, Sch Mech & Aerosp Engn, Singapore 639798, Singapore
关键词
heat exchanger; frost modeling; finned tube;
D O I
10.1016/j.applthermaleng.2005.04.009
中图分类号
O414.1 [热力学];
学科分类号
摘要
Frost accumulation on a heat exchanger, a direct result of combined heat and mass transfer between the moist air flowing across a cold surface, causes heat transfer performance degradation due to the insulating effect of frost layer and the coil blockage as the frost grows. The complex geometry of finned tube heat exchangers leads to uneven wall and air temperature distribution inside the coil, and causes variations of frost growth rate and densification along the coil. In this study, a general distributed model with frost formation was developed. The equations for finned tube heat exchanger were derived in non-steady-state manner and quasi-steady state in the frost model. In order to make the model more realistic, the variation of frost along fin due to uneven temperature distribution was included. The presented model is able to predict the dynamic behavior of an air cooler both under non-frost and frost condition. Comparisons were made based on the frost mass accumulation,. pressure drop across coil and energy transfer coefficient, and results were found to agree well with reported experimental results. (c) 2005 Published by Elsevier Ltd.
引用
收藏
页码:111 / 120
页数:10
相关论文
共 21 条
[1]  
AMEEN FR, 1993, ASHRAE TRAN, V99, P61
[2]   Experimental investigation on the performance of air cooler under frosting conditions [J].
Deng, DQ ;
Xu, L ;
Xu, SQ .
APPLIED THERMAL ENGINEERING, 2003, 23 (07) :905-912
[3]   GENERALIZED CORRELATION OF THE WATER FROST THERMAL-CONDUCTIVITY [J].
DIETENBERGER, MA .
INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 1983, 26 (04) :607-619
[4]   A DISTRIBUTED MODEL FOR PREDICTION OF THE TRANSIENT-RESPONSE OF AN EVAPORATOR [J].
JIA, X ;
TSO, CP ;
CHIA, PK ;
JOLLY, P .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 1995, 18 (05) :336-342
[5]   Distributed steady and dynamic modelling of dry-expansion evaporators [J].
Jia, X ;
Tso, CP ;
Jolly, P ;
Wong, YW .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 1999, 22 (02) :126-136
[6]   FROST FORMATION WITH VARYING ENVIRONMENTAL PARAMETERS [J].
JONES, BW ;
PARKER, JD .
JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME, 1975, 97 (02) :255-259
[7]   PERFORMANCE OF FINNED-TUBE HEAT-EXCHANGERS UNDER FROSTING CONDITIONS .2. COMPARISON OF EXPERIMENTAL-DATA WITH MODEL [J].
KONDEPUDI, SN ;
ONEAL, DL .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 1993, 16 (03) :181-184
[8]   PERFORMANCE OF FINNED-TUBE HEAT-EXCHANGERS UNDER FROSTING CONDITIONS .1. SIMULATION-MODEL [J].
KONDEPUDI, SN ;
ONEAL, DL .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 1993, 16 (03) :175-180
[9]  
KONDEPUDI SN, 1990, ASHRAE TRAN, V96, P439
[10]  
KONDEPUDI SN, 1989, ASME HTD, V123, P193