Removing Insertion Impedance Effects From Transformer Admittance Measurements

被引:8
作者
Gustavsen, Bjorn [1 ]
机构
[1] SINTEF Energy Res, N-7465 Trondheim, Norway
关键词
Admittance matrix; asymmetry; frequency domain; measurements; transformer; wideband;
D O I
10.1109/TPWRD.2011.2175818
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Frequency-domain measurements can be used for obtaining a wideband model of a power transformer via its terminal admittance matrix. This paper shows that the current sensor used in the measurements can significantly affect the elements of the obtained admittance matrix by its insertion impedance. The insertion impedance influences diagonal and off-diagonal elements, often leading to asymmetries in the matrix for transformers having a high-voltage ratio. Formulae are developed which are capable of removing these effects. The procedure is demonstrated for a distribution transformer.
引用
收藏
页码:1027 / 1029
页数:3
相关论文
共 3 条