Thermodynamic study of a novel solar LiBr/H2O absorption chiller

被引:32
作者
Li, Zeyu [1 ,2 ]
Jing, Yue [1 ,2 ]
Liu, Jinping [1 ,2 ]
机构
[1] South China Univ Technol, Sch Elect Power, Guangzhou 510640, Guangdong, Peoples R China
[2] South China Univ Technol, Guangdong Prov Key Lab High Efficient & Clean Ene, Guangzhou 510640, Guangdong, Peoples R China
基金
中国国家自然科学基金;
关键词
Solar cooling; Absorption; Thermodynamic; LiBr/H2O; COOLING SYSTEMS; PERFORMANCE ANALYSIS; DESIGN; ENERGY; WATER;
D O I
10.1016/j.enbuild.2016.10.022
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
A novel solar cooling system, i.e., the solar absorption-subcooled compression hybrid cooling system (SASCHCS), is a better solution for large-scale buildings with many floors, but the thermodynamic characteristics of the system are not adequately realized. The thermodynamic model of the hybrid system is absent, and the design of the nominal cooling capacity of the absorption subsystem and the volume of the storage tank are not known. Consequently, this paper primarily examined the thermodynamics of SASCHCS. A thermodynamic model of the hybrid system was developed, and the working process and performance of the hybrid system for different nominal cooling capacities of the absorption subsystem and the volumes of storage tanks were analysed in detail. The influence of selected parameters on the performance was discussed. It was found that the performance of the system first increases and subsequently decreases gradually with improvement in the nominal cooling capacity of the absorption subsystem. The appropriate ratio of the nominal cooling capacity of the absorption subsystem to the area of the collector should be 0.148 kW/m(2) to 0.222 kW/m(2). Additionally, the performance of the hybrid system increases first but subsequently decreases gradually with the decrease in volume of the storage tank. An appropriate decrease in the volume of the storage tank is recommended. This paper contributes to a deeper understanding of SASCHCS. (C) 2016 Elsevier B.V. All rights reserved.
引用
收藏
页码:565 / 576
页数:12
相关论文
共 29 条
  • [1] Design and experimental testing of the performance of an outdoor LiBr/H2O solar thermal absorption cooling system with a cold store
    Agyenim, Francis
    Knight, Ian
    Rhodes, Michael
    [J]. SOLAR ENERGY, 2010, 84 (05) : 735 - 744
  • [2] Solar driven cooling systems: An updated review
    Allouhi, A.
    Kousksou, T.
    Jamil, A.
    Bruel, P.
    Mourad, Y.
    Zeraouli, Y.
    [J]. RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2015, 44 : 159 - 181
  • [3] Design and performance of solar powered absorption cooling systems in office buildings
    Eicker, Ursula
    Pietruschka, Dirk
    [J]. ENERGY AND BUILDINGS, 2009, 41 (01) : 81 - 91
  • [4] Economical comparison between a solar-powered vapour absorption air-conditioning system and a vapour compression system in the Middle East
    Elsafty, A
    Al-Daini, AJ
    [J]. RENEWABLE ENERGY, 2002, 25 (04) : 569 - 583
  • [5] Comparative study of different solar cooling systems for buildings in subtropical city
    Fong, K. F.
    Chow, T. T.
    Lee, C. K.
    Lin, Z.
    Chan, L. S.
    [J]. SOLAR ENERGY, 2010, 84 (02) : 227 - 244
  • [6] Second law comparison of single effect and double effect vapour absorption refrigeration systems
    Gomri, Rabah
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2009, 50 (05) : 1279 - 1287
  • [7] He L.J., 2013, J ENG THERMOPHYS, V34, P814
  • [8] [何丽娟 He Lijuan], 2013, [太阳能学报, Acta Energiae Solaris Sinica], V34, P1177
  • [9] Energy, exergy, economic and environmental (4E) analyses based comparative performance study and optimization of vapor compression-absorption integrated refrigeration system
    Jain, Vaibhav
    Sachdeva, Gulshan
    Kachhwaha, Surendra Singh
    [J]. ENERGY, 2015, 91 : 816 - 832
  • [10] Optimum hot water temperature for absorption solar cooling
    Lecuona, A.
    Ventas, R.
    Venegas, M.
    Zacarias, A.
    Salgado, R.
    [J]. SOLAR ENERGY, 2009, 83 (10) : 1806 - 1814