Optimal sizing of a utility-scale energy storage system in transmission networks to improve frequency response

被引:45
作者
Das, Choton K. [1 ]
Mahmoud, Thair S. [1 ]
Bass, Octavian [1 ]
Muyeen, S. M. [2 ]
Kothapalli, Ganesh [1 ]
Baniasadi, Ali [1 ]
Mousavi, Navid [1 ]
机构
[1] Edith Cowan Univ ECU, Sch Engn, 270 Joondalup Dr, Perth, WA 6027, Australia
[2] Curtin Univ, Sch Elec Engn Comp & Math Sci EECMS, Perth, WA 6102, Australia
关键词
Change of frequency; Energy storage system; Battery sizing; Frequency response; Frequency deviation; Transmission network planning; IEEE 39 bus data; ROCOF; Frequency nadir; PSO; Artificial bee colony; DIgSILENT PowerFactory; Generator dispatch; Fitness-scaled chaotic; Controller tuning; Hybrid meta-heuristic; BESS; Battery storage; BATTERY; PLACEMENT; STRATEGY;
D O I
10.1016/j.est.2020.101315
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The frequency response of a large power system is affected by the penetration of renewable energy sources (RESs), where a utility-scale energy storage system (ESS) can alleviate the problem. This paper presents a strategy for sizing an ESS to improve frequency response of transmission networks. The location of the ESS in the transmission network is determined through a sensitivity analysis targeting minimum line loading around a bus. The ESS sizing strategy considers the minimization of frequency deviation as well as rate of change of frequency (ROCOF) after generator or load tripping events. The tuning of PQ controller parameters of the ESS (active power part) is also performed for frequency response improvement. The proposed approach is tested in a modified IEEE-39 bus power system considering a variety of scenarios where RESs are integrated as four different schemes for peak and off-peak load conditions. DIgSILENT PowerFactory is used for developing, testing, and analyzing the system models. A fitness-scaled chaotic artificial bee colony (FSCABC) optimization algorithm (a hybrid meta-heuristic approach) is used for optimization through a Python script automating simulation events in PowerFactory. The results obtained from the FSCABC approach are verified through the application of a particle swarm optimization algorithm. The simulation results suggest that the proposed ESS sizing technique including ESS controller tuning can successfully improve the frequency response of a transmission network.
引用
收藏
页数:22
相关论文
共 38 条
[1]  
AEMC, 2016, EPR0053 AEMC
[2]  
Alhejaj SM, 2016, 2016 IEEE INTERNATIONAL CONFERENCE ON POWER SYSTEM TECHNOLOGY (POWERCON)
[3]  
[Anonymous], REN 2018 GLOB STAT R
[4]  
[Anonymous], 2018, INITIAL OPERATION HO, DOI DOI 10.1111/FCRE.12333
[5]  
[Anonymous], 2018, 39 BUS NEW ENGLAND S
[6]  
[Anonymous], 2013, NRELPR6A2058703
[7]   Optimal sizing design and operation of electrical and thermal energy storage systems in smart buildings [J].
Baniasadi, Ali ;
Habibi, Daryoush ;
Al-Saedi, Waleed ;
Masoum, Mohammad A. S. ;
Das, Choton K. ;
Mousavi, Navid .
JOURNAL OF ENERGY STORAGE, 2020, 28
[8]  
Battery Energy Storing System Template, 2018, BATTERY ENERGY STORI
[9]  
Das C.K., 2019, SMART MANAGEMENT STR
[10]   An optimal allocation and sizing strategy of distributed energy storage systems to improve performance of distribution networks [J].
Das, Choton K. ;
Bass, Octavian ;
Mahmoud, Thair S. ;
Kothapalli, Ganesh ;
Masoum, Mohammad A. S. ;
Mousavi, Navid .
JOURNAL OF ENERGY STORAGE, 2019, 26