Investigation on the Energy Saving Potential of Using a Novel Dew Point Cooling System in Data Centres

被引:11
|
作者
Bi, Yin [1 ,2 ]
Wang, Yugang [1 ,3 ]
Ma, Xiaoli [1 ]
Zhao, Xudong [1 ]
机构
[1] Univ Hull, Sch Engn & Comp Sci, Kingston Upon Hull HU6 7RX, Yorks, England
[2] Guangdong Univ Technol, Sch Civil & Transportat Engn, Guangzhou 510006, Guangdong, Peoples R China
[3] Jimei Univ, Sch Mech & Energy Engn, Xiamen 361021, Peoples R China
来源
ENERGIES | 2017年 / 10卷 / 11期
基金
英国工程与自然科学研究理事会; 欧盟地平线“2020”;
关键词
dew point cooling; data centres; energy saving; energy usage effectiveness; cooling load; INDIRECT EVAPORATIVE COOLER; COUNTER-FLOW; HEAT-EXCHANGERS; PERFORMANCE; OPTIMIZATION; CONSERVATION;
D O I
10.3390/en10111732
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Information technology (IT) has brought significant changes in people's lives. As an important part of the IT industry, data centres (DCs) have been rapidly growing in both the number and size over the past 40 years. Around 30% to 40% of electricity consumption in DCs is used for space cooling, thus leading to very inefficient DC operation. To identify ways to reduce the energy consumption for space cooling and increase the energy efficiency of DCs' operation, a dedicated investigation into the energy usage in DCs has been undertaken and a novel high performance dew point cooling system was introduced into a DC operational scheme. Based on the cooling load in DCs, a case study was carried out to evaluate the energy consumptions and energy usage effectiveness when using the novel dew point cooling system in different scales of DCs in various climates. It was found that by using the novel dew point cooling system, for 10 typical climates a DC can have a much lower power usage effectiveness (PUE) of 1.10 to 1.22 compared to that of 1.7 to 3.7 by using existing traditional cooling systems, leading to significantly increased energy efficiency of the DC operation. In addition, the energy performance by managing the cooling air supply at the different levels in DCs, i.e., room, row and rack level, was simulated by using a dynamic computer model. It was found that cooling air supply at rack level can provide a higher energy efficiency in DCs. Based on the above work, the energy saving potential in DCs was conducted by comparing DCs using an the novel dew point cooling system and the optimum management scheme for the cooling air supply to that using traditional air cooling systems and the same supply air management. Annual electricity consumptions for the two cases were given. It was found that by using the novel dew point cooling system and optimum management system for the cooling air supply, an 87.7-91.6% electricity consumption saving for space cooling in DCs could be achieved in 10 typical cities at 10 selected climatic conditions.
引用
收藏
页数:21
相关论文
共 50 条
  • [1] Investigation of energy saving potential for data centres based on load profile
    Bi, Y.
    Zhao, X.
    PROCEEDINGS OF THE 8TH INTERNATIONAL CONFERENCE ON FUTURE ENERGY SYSTEMS (E-ENERGY'17), 2017, : 271 - 277
  • [2] Real life test of a novel super performance dew point cooling system in operational live data centre
    Ma, Xiaoli
    Zeng, Cheng
    Zhu, Zishang
    Zhao, Xudong
    Xiao, Xin
    Akhlaghi, Yousef Golizadeh
    Shittu, Samson
    APPLIED ENERGY, 2023, 348
  • [3] Analytical Investigation of a Novel System for Combined Dew Point Cooling and Water Recovery
    Cichon, Aleksandra
    Worek, William
    APPLIED SCIENCES-BASEL, 2021, 11 (04): : 1 - 18
  • [4] Experimental and numerical investigation of a dew-point cooling system for thermal comfort in buildings
    Jradi, M.
    Riffat, S.
    APPLIED ENERGY, 2014, 132 : 524 - 535
  • [5] An experimental study of a novel dew point evaporative cooling system
    Riangvilaikul, B.
    Kumar, S.
    ENERGY AND BUILDINGS, 2010, 42 (05) : 637 - 644
  • [6] Numerical study of a novel, dew point evaporative cooling system
    Riangvilaikul, B.
    Kumar, S.
    ENERGY AND BUILDINGS, 2010, 42 (11) : 2241 - 2250
  • [7] The possibility of using a novel dew point air cooling system (M-Cycle) for A/C application in Arab Gulf Countries
    Baakeem, Saleh S.
    Orfi, Jamel
    Mohamad, Abdulmajeed
    Bawazeer, Saleh
    BUILDING AND ENVIRONMENT, 2019, 148 : 185 - 197
  • [8] Energy saving potential of using heat pipes for CPU cooling
    Wang, Yabo
    Wang, Bin
    Zhu, Kai
    Li, Hailong
    He, Wei
    Liu, Shengchun
    APPLIED THERMAL ENGINEERING, 2018, 143 : 630 - 638
  • [9] Operating energy savings in a liquid desiccant and dew point evaporative cooling-assisted 100% outdoor air system
    Ham, Sang-Woo
    Lee, Sung-Joon
    Jeong, Jae-Weon
    ENERGY AND BUILDINGS, 2016, 116 : 535 - 552
  • [10] Numerical simulation of a novel energy-efficient dew-point evaporative air cooler
    Cui, X.
    Chua, K. J.
    Yang, W. M.
    APPLIED ENERGY, 2014, 136 : 979 - 988