Characterization of an effervescent atomization water mist nozzle and its fire suppression tests

被引:45
作者
Huang, X. [1 ,2 ]
Wang, X. S. [1 ]
Liao, G. X. [1 ]
机构
[1] Univ Sci & Technol China, State Key Lab Fire Sci, Hefei 230026, Peoples R China
[2] Minist Publ Secur, Tianjin Fire Res Inst, Tianjin 300381, Peoples R China
关键词
Effervescent atomization; Two-phase flow; Water mist; Fire suppression; POOL FIRES; FLOW;
D O I
10.1016/j.proci.2010.06.001
中图分类号
O414.1 [热力学];
学科分类号
摘要
A gas-outside-liquid-inside water mist nozzle based on effervescent atomization technology is designed, characterized and tested in this paper. The droplets size distribution, velocity under different operation pressures and gas-liquid-ratios (GLR) are measured with a Phase Doppler Analyser (PDA). The gas flow rate, liquid flow rate of the nozzle with one or seven orifices are also characterized under different operation pressures and GLR conditions, respectively. The results show that all of above parameters are mainly influenced by GLR, i.e., the larger the GLR is, the smaller the droplet size will be, and the liquid mass flow rate is exponentially increased with the increasing of GLR. The test results of fire suppression show that this gas-outside-liquid-inside effervescent atomizer works well for fire extinguishment except the cases where the liquid flow rate is less than about 70 kg/h and the gas pressure is lower than 0.3 MPa. (C) 2010 The Combustion Institute. Published by Elsevier Inc. All rights reserved.
引用
收藏
页码:2573 / 2579
页数:7
相关论文
共 19 条
[1]  
Alpert R.L., 1993, 5207 NISTIR, P31
[2]  
Bachalo W.D., 1993, 5207 NISTIR BUILD FI, P75
[3]  
Cdubizu C., 1998, FIRE SAFETY J, V31, P253
[4]   Visualization of two phase flow inside an effervescent atomizer [J].
Huang, X. ;
Wang, X. ;
Liao, G. .
JOURNAL OF VISUALIZATION, 2008, 11 (04) :299-308
[5]  
Huang X., 2007, THESIS U SCI TECHNOL
[6]   Fire protection of heritage structures: Use of a portable water mist system under high-altitude conditions [J].
Huang, Xin ;
Wang, Xishi ;
Jin, Xiang ;
Liao, Guangxuan ;
Qin, Jun .
JOURNAL OF FIRE SCIENCES, 2007, 25 (03) :217-239
[7]   DISCUSSIONS ON THE USE OF FINE WATER SPRAYS OR MISTS FOR FIRE SUPPRESSION [J].
JONES, A ;
NOLAN, PF .
JOURNAL OF LOSS PREVENTION IN THE PROCESS INDUSTRIES, 1995, 8 (01) :17-22
[8]  
Kim JY, 2001, ATOMIZATION SPRAY, V11, P735
[9]  
Liu Zhigang, 1999, J. Fire Protect. Eng., V10, P32, DOI [10.1177/104239159901000303, DOI 10.1177/104239159901000303]
[10]  
Lund M.T., 1993, ATOMIZATION SPRAY, V3, P77, DOI [10.1615/atomizspr.v3.i1.40, DOI 10.1615/AT0MIZSPR.V3.I1.40]