A Novel Voltage Clamping-Based Overvoltage Protection Strategy to Avoid Spurious Trip of Inverter-Based Resources and Eliminate the Risk of Wildfire Following the REFCL Operation in Compensated Networks

被引:6
作者
Jalilian, Amin [1 ]
Muttaqi, Kashem M. [1 ]
Sutanto, Danny [1 ]
机构
[1] Univ Wollongong, Sch Elect Comp & Telecommun Engn, Wollongong, NSW 2522, Australia
基金
澳大利亚研究理事会;
关键词
Voltage control; Fires; Inverters; Circuit faults; Transient analysis; Australia; Fault currents; DC reverse current; inverter-based resources (IBR); overvoltage protection; power electronics; rapid earth fault current limiter (REFCL); voltage clamping; wildfires;
D O I
10.1109/TIA.2021.3089116
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
This article investigates the operational performance of the rapid earth fault current limiter (REFCL) that has been employed in Australia to reduce the risk of wildfires and shows that after the REFCL activation, an overvoltage is imposed on the grid which can lead to wildfire by creating a cross-country fault. Moreover, by increasing the penetration level of the inverter-based resources (IBRs), the potential inverter trip on transient overvoltage can become a vital issue. Since the protection functions of the IBRs are very sensitive to any transient overvoltage, their overvoltage or dc reverse current protection functions will trip the IBRs immediately following any overvoltage condition such as those caused during the REFCL operation. To tackle the mentioned problems, a novel voltage clamping-based overvoltage protection strategy is proposed and developed through a smart power electronic topology. The article presents the analytical analysis and the mode of operation of the proposed overvoltage protection strategy. The effectiveness of the proposed overvoltage protection strategy is tested through a comprehensive set of simulation studies in Power System Computer-Aided Design/Electromagnetic Transients including DC (PSCAD/EMTDC). The simulation results show that the proposed strategy can immediately limit the magnitude of the overvoltage, thereby it can not only reduce the risk of cross-country faults and wildfires but it can also mitigate the spurious trips of the IBRs.
引用
收藏
页码:4558 / 4568
页数:11
相关论文
共 20 条
[1]  
[Anonymous], 2018, HV CUST POL REFCL PR
[2]  
[Anonymous], 2020, STATISTA
[3]  
[Anonymous], 2020, AUSTR BUSHF 5 THINGS
[4]  
Baughman M. L, 2011, IEEE AFRICON 11, P1, DOI [10.1109/AFRCON.2011.6072095, DOI 10.1109/AFRCON.2011.6072095]
[5]  
Choobineh M., 2016, P 2016 IEEE POW EN S, P1
[6]   Reclosing of Distribution Systems for Wildfire Prevention [J].
Davoudi, Masoud ;
Efaw, Brett ;
Avendano-Mora, Manuel ;
Lauletta, John L. ;
Huffman, Gary B. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2021, 36 (04) :2298-2307
[7]  
Haddadi A., 2020, SAND20200265 683084
[8]  
Jalilian A., 2014, IEEE T POWER, V29, P62
[9]   A Novel Voltage Clamping based Overvoltage Protection Strategy to Avoid Spurious Trip of Inverter based Resources and Eliminate the Risk of Bushfires following the REFCL Operation [J].
Jalilian, Amin ;
Muttaqi, Kashem M. ;
Sutanto, Danny .
2020 IEEE INDUSTRY APPLICATIONS SOCIETY ANNUAL MEETING, 2020,
[10]   Current-based directional relaying scheme to protect series compensated transmission lines used to transmit bulk power produced by power electronics interfaced renewable energy power plants [J].
Jalilian, Amin ;
Muttaqi, Kashem M. .
IET GENERATION TRANSMISSION & DISTRIBUTION, 2020, 14 (15) :2976-2987