Offshore underwater substation for wave energy converter arrays

被引:31
作者
Rahm, M. [1 ]
Bostrom, C. [1 ]
Svensson, O. [1 ]
Grabbe, M. [1 ]
Bulow, F. [1 ]
Leijon, M. [1 ]
机构
[1] Uppsala Univ, Div Elect, Swedish Ctr Renewable Elect Energy Convers, Uppsala, Sweden
关键词
GENERATOR; DESIGN; SYSTEM;
D O I
10.1049/iet-rpg.2009.0180
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
In this study, the design, construction, deployment and operation of an offshore underwater substation is discussed The seabed placed substation interconnects three linear generator wave energy converters (WECs) at the Swedish Lysekil wave energy research site The power from the WECs fluctuates because of their direct-driven topology The generator voltage has varying electrical frequency and amplitude To reduce the fluctuations, the individual voltages of the WECs are rectified and the power is added on a common DC-bus in the substation The voltage is inverted, transformed and power is transmitted to an on-shore resistive load The substation was retrieved on two occasions since the deployment in the spring of 2009 The functionality of the substation is validated by comparing voltage and current wave forms from Simulink with measured results from laboratory experiments In addition, a sample of results from real offshore operation is illustrated and discussed With a proportional-integral-derivative (PID)-regulator in the inverter control, the small fluctuations in the DC-bus voltage could be minimised However, this would reduce the energy storage capability of the DC-link smoothing capacitors
引用
收藏
页码:602 / 612
页数:11
相关论文
共 29 条
[1]   Offshore substation [J].
Bazargan, Masoud .
POWER ENGINEER, 2007, 21 (03) :26-27
[2]   Experimental results of rectification and filtration from an offshore wave energy system [J].
Bostrom, C. ;
Lejerskog, E. ;
Stalberg, M. ;
Thorburn, K. ;
Leijon, M. .
RENEWABLE ENERGY, 2009, 34 (05) :1381-1387
[3]   Study of a Wave Energy Converter Connected to a Nonlinear Load [J].
Bostrom, Cecilia ;
Waters, Rafael ;
Lejerskog, Erik ;
Svensson, Olle ;
Stalberg, Magnus ;
Stromstedt, Erland ;
Leijon, Mats .
IEEE JOURNAL OF OCEANIC ENGINEERING, 2009, 34 (02) :123-127
[4]   Power conditioning of the output from a linear vernier hybrid permanent magnet generator for use in direct drive wave energy converters [J].
Brooking, PRM ;
Mueller, MA .
IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 2005, 152 (05) :673-681
[5]   Voltage control performance of AWS connected for grid operation [J].
Das, Biswarup ;
Pal, Bikash C. .
IEEE TRANSACTIONS ON ENERGY CONVERSION, 2006, 21 (02) :353-361
[6]   Simulations and experiments on a 12 kW direct driven PM synchronous generator for wind power [J].
Eriksson, Sandra ;
Solum, Andreas ;
Leijon, Mats ;
Bernhoff, Hans .
RENEWABLE ENERGY, 2008, 33 (04) :674-681
[7]  
*EUR STAD UNF PRES, 2009, 13445 EN
[8]   OCEAN WAVE ENERGY [J].
FALNES, J ;
LOVSETH, J .
ENERGY POLICY, 1991, 19 (08) :768-775
[9]  
Frigaard P., 2004, P 14 ANN INT OFFSH P
[10]  
GILLANDERS K, 2005, P 6 EUR WAV TID EN C