Internal dropwise condensation: Modeling and experimental framework for horizontal tube condensers

被引:14
作者
Cheng, Kuok [1 ]
Kim, Sunwoo [2 ]
Lee, Sangsoo [3 ]
Kim, Kwang J. [4 ]
机构
[1] Univ Nevada, Dept Mech Engn, Reno, NV 89557 USA
[2] Univ Alaska, Dept Mech Engn, Fairbanks, AK 99701 USA
[3] Texas A&M Univ, Dept Mech & Ind Engn, Kingsville, TX USA
[4] Univ Nevada, Dept Mech Engn, Act Mat & Smart Living Lab, Las Vegas, NV 89154 USA
基金
美国国家科学基金会;
关键词
Internal condensation; Dropwise condensation; Dropwise condensation promoter; Hydrophobic coatings; Internal dropwise condensation model; HEAT-TRANSFER; PRESSURE-DROP; HFC-134A; SMOOTH; FLUIDS;
D O I
10.1016/j.ijheatmasstransfer.2014.11.084
中图分类号
O414.1 [热力学];
学科分类号
摘要
Many researches have been focused on internal condensation with machined microstructure patterns on internal surfaces that can improve heat transfer performance up to 400% comparing to smooth surfaces. However, microstructure patterns are not effective for all geometries such as micro-channels and other complicated shapes. This study uses a dropwise condensation (DWC) promoter that can be easily applied to different geometries to improve internal condensation heat transfer. The main objectives of this study are to investigate internal condensation heat transfer by the dropwise condensation promoter via (i) developing an internal dropwise condensation model and (ii) conducting internal condensation experiments with the dropwise condensation promoter. The dropwise condensation model was modified to the available internal condensation model. The experiments for internal steam condensation were conducted for aluminum and copper tubes with external fins and an internal coating for dropwise condensation. The experimental results are compared to the results from several correlations in the literature and the model developed in this study. It is found that most correlations in the literature overestimate internal condensation heat transfer coefficients at low mass fluxes. The dropwise condensation model shows that dropwise condensation promoters can enhance internal condensation heat transfer coefficients. This conclusion is verified by experimental results demonstrating that the hydrophobic dropwise condensation promoter used in this study can enhance internal condensation heat transfer coefficients by 50%. (C) 2014 Elsevier Ltd. All rights reserved.
引用
收藏
页码:99 / 108
页数:10
相关论文
共 30 条
[1]   Azeotropy in the natural and synthetic refrigerant mixtures [J].
Artemenko, Sergey ;
Mazur, Victor .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2007, 30 (05) :831-839
[2]  
Bergelin O. P., 1946, M BERK CAL US JUN AS, P19
[3]  
Bivens D B., 1994, International Refrigeration Conference, P299
[4]  
BRIGGS A, 1998, EXP J HEAT TRANSFER, P163
[5]  
Briggs A., 1998, P 11 IHTC AUG 23 28
[6]  
Calm J.M., 2007, HPAC Eng (Heat Pip Air Cond), P50
[7]   Condensation inside and outside smooth and enhanced tubes - a review of recent research [J].
Cavallini, A ;
Censi, G ;
Del Col, D ;
Doretti, L ;
Longo, GA ;
Rossetto, L ;
Zilio, C .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2003, 26 (04) :373-392
[8]  
Cavallini A, 1999, J ENHANC HEAT TRANSF, V6, P441
[9]  
Collier J.G., 1994, Convective boiling and condensation
[10]  
Didi MBO, 2002, INT J REFRIG, V25, P935