Directional Fault Detection Based on Active Power Coefficient in Resonant-Earthed Distribution System
被引:0
作者:
Liu, Yuanlong
论文数: 0引用数: 0
h-index: 0
机构:
Shandong Univ, Sch Elect Engn, Jinan 250100, Peoples R China
Shandong Siji Technol Co LTD, Jinan 250021, Peoples R ChinaShandong Univ, Sch Elect Engn, Jinan 250100, Peoples R China
Liu, Yuanlong
[1
,3
]
Zhang, Hengxu
论文数: 0引用数: 0
h-index: 0
机构:
Shandong Univ, Sch Elect Engn, Jinan 250100, Peoples R ChinaShandong Univ, Sch Elect Engn, Jinan 250100, Peoples R China
Zhang, Hengxu
[1
]
Wang, Pengwei
论文数: 0引用数: 0
h-index: 0
机构:
Shandong Univ Technol, Coll Elect & Elect Engn, Zibo 255000, Peoples R ChinaShandong Univ, Sch Elect Engn, Jinan 250100, Peoples R China
Wang, Pengwei
[2
]
Xu, Bingyin
论文数: 0引用数: 0
h-index: 0
机构:
Shandong Univ Technol, Coll Elect & Elect Engn, Zibo 255000, Peoples R ChinaShandong Univ, Sch Elect Engn, Jinan 250100, Peoples R China
Xu, Bingyin
[2
]
机构:
[1] Shandong Univ, Sch Elect Engn, Jinan 250100, Peoples R China
[2] Shandong Univ Technol, Coll Elect & Elect Engn, Zibo 255000, Peoples R China
[3] Shandong Siji Technol Co LTD, Jinan 250021, Peoples R China
Earthing Fault;
Active Power Coefficient;
Frequency Band;
Intermittent Fault;
Measurement Error of Current Transformer;
D O I:
10.1166/jno.2022.3195
中图分类号:
TM [电工技术];
TN [电子技术、通信技术];
学科分类号:
0808 ;
0809 ;
摘要:
Transients-based earth fault protections cannot trip reliably for earthing faults with high resistance in a small current distribution system due to low magnitude of the high-frequency transient signals. Directional protection based on zero-sequence active power can trip reliably only with the presence of damping resistor during fault, and can be used as back-up protection. Phase comparison method is not applicable to arcing fault and intermittent fault. Energy method also has a drawback because of its vulnerability to current transformer error. This method which use the active power coefficient of the zero-sequence signal which is lower than 100 Hz is proposed. This method determines the faulty point direction through this coefficient. Digital simulation and actual fault recordings data have verified the feasibility of the proposed method, and is not subject to measurement error of current transformer.