Investigation on wind tunnel tests of a full aeroelastic model of electrical transmission tower-line system

被引:88
作者
Liang, Shuguo [1 ]
Zou, Lianghao [1 ]
Wang, Dahai [2 ]
Cao, Hong [3 ]
机构
[1] Wuhan Univ, Sch Civil & Bldg Engn, Wuhan 430072, Peoples R China
[2] Wuhan Univ Technol, Sch Civil & Architecture Engn, Wuhan 430070, Peoples R China
[3] Div Local Assistance, Sacramento, CA 94274 USA
基金
美国国家科学基金会;
关键词
Electrical transmission tower-line system; Wind tunnel tests; Aeroelastic model; Wind-induced responses; INDUCED VIBRATION; BEHAVIOR; FAILURE;
D O I
10.1016/j.engstruct.2014.11.042
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
A full aeroelastic model with one tower two lines to simulate electrical transmission tower-line system was established. Displacements and accelerations of the aeroelastic model of the tower with and without lines under various wind speeds were investigated through boundary layer wind tunnel tests, and the maximum wind loads on, and wind-induced destroyed mode of, the tower-line model were also observed. Meanwhile, the static and dynamic loads on electrical transmission tower transferred from lines were acquired by measuring the strains of the insulators at the ends of lines. The effects of coupling between electrical transmission tower and line on wind-induced vibrations of electrical transmission towers were investigated, and the pattern of wind induced responses along with wind speeds, as well as the characteristics of spectra of wind induced dynamic responses, of the aeroelastic model of the tower with and without line were analyzed. The experimental results indicate that the effects of coupling between transmission tower and line on wind-induced responses of the tower, as well as the across-wind vibration of the tower, must take into consideration in the wind-resistant design of electrical transmission tower; and the reinforcement at the weak parts of electrical transmission tower could effectively increase the survival ability of the tower under strong wind. (C) 2014 Elsevier Ltd. All rights reserved.
引用
收藏
页码:63 / 72
页数:10
相关论文
共 30 条
[1]   Upgrading of transmission towers using a diaphragm bracing system [J].
Albermani, F ;
Mahendran, M ;
Kitipornchai, S .
ENGINEERING STRUCTURES, 2004, 26 (06) :735-744
[2]   Failure analysis of transmission towersd [J].
Albermani, F. ;
Kitipornchai, S. ;
Chan, R. W. K. .
ENGINEERING FAILURE ANALYSIS, 2009, 16 (06) :1922-1928
[3]   Numerical simulation of structural behaviour of transmission towers [J].
Albermani, FGA ;
Kitipornchai, S .
THIN-WALLED STRUCTURES, 2003, 41 (2-3) :167-177
[4]  
American Society of Civil Engineers, 2009, ASCE MAN REP ENG PRA, V74
[5]  
[Anonymous], 2003, 60826 CEIIEC
[6]   Dynamic behavior and stability of transmission line towers under wind forces [J].
Battista, RC ;
Rodrigues, RS ;
Pfeil, MS .
JOURNAL OF WIND ENGINEERING AND INDUSTRIAL AERODYNAMICS, 2003, 91 (08) :1051-1067
[7]  
British Standard, 1994, GUID LOAD STRENGTH O
[8]  
Davenport A.G., 1979, Fifth International Conference on Wind Engineering, 1979, P899
[9]  
Deng Hong-zhou, 2003, Journal of Tongji University (Natural Science), V31, P132
[10]   Dynamic analysis of the transmission line crossing "Lago de Maracaibo" [J].
Diana, G ;
Bruni, S ;
Cheli, F ;
Fossati, F ;
Manenti, A .
JOURNAL OF WIND ENGINEERING AND INDUSTRIAL AERODYNAMICS, 1998, 74-6 :977-986