The sensitivity of chiller performance to common faults

被引:65
作者
Comstock, MC [1 ]
Braun, JE
Groll, EA
机构
[1] Lexmark Int, Lexington, KY USA
[2] Purdue Univ, Ray W Herrick Labs, W Lafayette, IN 47907 USA
来源
HVAC&R RESEARCH | 2001年 / 7卷 / 03期
关键词
D O I
10.1080/10789669.2001.10391274
中图分类号
O414.1 [热力学];
学科分类号
摘要
In the development of automated fault detection and diagnostics (FDD), it is important to identify the most appropriate sensors for the faults that can occur. This paper presents data and results that provide a basis for development of fully automated FDD applied to chillers. Faults that can be detected and diagnosed with relatively low cost sensors were experimentally simulated in the laboratory and the sensitivities of different measurements to each fault were identified The fault testing led to a set of generic rules for the impacts of faults on measurements that could be used for fault diagnoses. The impacts of the faults on cooling capacity and coefficient of performance (COP) were also evaluated. Based upon the! results, all of the faults were found to be significant at the levels introduced and should he detectable and diagnosable by an FDD system using low cost measurements. The data set obtained during this work is very comprehensive and can be used to design and evaluate the performance of FDD methods.
引用
收藏
页码:263 / 279
页数:17
相关论文
共 12 条
[1]  
*ARI, 1992, 550 ARI
[2]  
Bailey M.B., 1998, THESIS U COLORADO
[3]   Common faults and their impacts for rooftop air conditioners [J].
Breuker, MS ;
Braun, JE .
HVAC&R RESEARCH, 1998, 4 (03) :303-318
[4]   Evaluating the performance of a fault detection and diagnostic system for vapor compression equipment [J].
Breuker, MS ;
Braun, JE .
HVAC&R RESEARCH, 1998, 4 (04) :401-425
[5]  
Comstock M.C., 1999, HL9918 PURD U RW HER
[6]  
Comstock M.C., 1999, HL9920 PURD U RW HER
[7]  
COMSTOCK MC, 1999, HL9919 PURD U RW HER
[8]   ONLINE FAILURE DIAGNOSIS FOR COMPRESSION REFRIGERATION PLANTS [J].
GRIMMELIUS, HT ;
WOUD, JK ;
BEEN, G .
INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 1995, 18 (01) :31-41
[9]  
Peitsman HC, 1996, ASHRAE TRAN, V102, P628
[10]  
STOUPPE DE, 1989, NATL ENG, V93, P14