A new PID load frequency controller design method in frequency domain through direct synthesis approach

被引:106
作者
Anwar, Md Nishat [1 ]
Pan, Somnath [1 ]
机构
[1] Indian Sch Mines, Dept Elect Engn, Dhanbad 826004, Bihar, India
关键词
PID controller; Load frequency control (LFC); Frequency response matching; Load-disturbance rejection; Direct synthesis (DS); AUTOMATIC-GENERATION CONTROL; POWER-SYSTEM; AREA;
D O I
10.1016/j.ijepes.2014.12.024
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In this paper a new PID controller design method based on the direct synthesis (DS) approach of controller design in frequency domain is presented. The parameters of the PID controller are obtained through frequency response matching with the DS controller. The method yields linear algebraic equations, solution of which gives the controller parameters. The design method has been developed for single-area as well as multi-area power systems. Non-linearity like the generation rate constraint (GRC) has been considered. Several examples are taken from the literature to demonstrate the effectiveness of the proposed method in comparison with some prevalent design methods. (C) 2014 Elsevier Ltd. All rights reserved.
引用
收藏
页码:560 / 569
页数:10
相关论文
共 32 条
[1]   BFOA based design of PID controller for two area Load Frequency Control with nonlinearities [J].
Ali, E. S. ;
Abd-Elazim, S. M. .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2013, 51 :224-231
[2]   A new load frequency control approach in an isolated small power systems using coefficient diagram method [J].
Ali, Raheel ;
Mohamed, Tarek Hassan ;
Qudaih, Yaser Soliman ;
Mitani, Y. .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2014, 56 :110-116
[3]   Robust controller design for automatic generation control based on Q-parameterization [J].
Azzam, M ;
Mohamed, YS .
ENERGY CONVERSION AND MANAGEMENT, 2002, 43 (13) :1663-1673
[4]   Variable structure fuzzy gain scheduling based load frequency controller for multi source multi area hydro thermal system [J].
Chandrakala, K. R. M. Vijaya ;
Balamurugan, S. ;
Sankaranarayanan, K. .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2013, 53 :375-381
[5]   PI/PID controller design based on direct synthesis and disturbance rejection [J].
Chen, D ;
Seborg, DE .
INDUSTRIAL & ENGINEERING CHEMISTRY RESEARCH, 2002, 41 (19) :4807-4822
[6]  
Concordia C., 1953, Trans. Am. Inst. Electr. Eng Part. III Power Appar. Syst, V72, P562, DOI [10.1109/AIEEPAS.1954.4498803, DOI 10.1109/AIEEPAS.1953.4498667]
[7]   AUTOMATIC-GENERATION CONTROL OF A HYDROTHERMAL SYSTEM WITH NEW AREA CONTROL ERROR CONSIDERING GENERATION RATE CONSTRAINT [J].
DAS, D ;
NANDA, J ;
KOTHARI, ML ;
KOTHARI, DP .
ELECTRIC MACHINES AND POWER SYSTEMS, 1990, 18 (06) :461-471
[8]  
Debbarma S, 2013, ISA T
[9]   OPTIMUM MEGAWATT-FREQUENCY CONTROL OF MULTIAREA ELECTRIC ENERGY SYSTEMS [J].
ELGERD, OI ;
FOSHA, CE .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1970, PA89 (04) :556-&
[10]  
Gundes AN, 2013, AM CONTR C ACC WASH