A Hybrid Flexible Neutral Grounding Mode for Large Generators

被引:1
作者
Wang, Yikai [1 ]
Yin, Xin [2 ]
Yin, Xianggen [1 ]
Qiao, Jian [1 ]
Tan, Liming [1 ]
机构
[1] Huazhong Univ Sci & Technol, State Key Lab Adv Elect Engn & Technol, 1037 Luoyu Rd, Wuhan 430074, Peoples R China
[2] Univ Liverpool, Dept Elect Engn & Elect, Liverpool L69 3BX, Merseyside, England
基金
中国国家自然科学基金;
关键词
arc suppression; hybrid grounding; dual frequency; inverter capacity; fault type; ARC SUPPRESSION DEVICE; FAULT PROTECTION; PRINCIPLE; UNIT;
D O I
10.3390/machines10080684
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Single-phase ground faults frequently occur at the generator stator windings. To realize reliable arc suppression, a dual-frequency active arc-suppression strategy has been widely considered. However, the existing method needs an inverter with large capacity, which is large in volume and high in cost, causing limited engineering application prospects. To reduce the capacity, a novel hybrid flexible neutral grounding method for large generators is proposed in this paper. It combines the dual-frequency active arc-suppression strategy with the arc-suppression coil-grounding mode. Thus, most of the fundamental components in the fault current are compensated by the arc-suppression coil, and the rest are compensated by the active arc-suppression device. The capacity of the inverter can be greatly reduced under the premise of reliably realizing arc suppression. To identify transient and permanent ground faults after arc suppression, the phase-angle relation between the third-harmonic voltage and current variation at the generator neutral point is used to form the fault-type identification criterion. The third-harmonic quantities can avoid the blind area at the neutral point caused by fundamental quantities. Simulation and experimental test results verify the effectiveness of the proposed method.
引用
收藏
页数:15
相关论文
共 22 条
  • [1] Minimising the risk of cross-country faults in systems using arc suppression coils
    Burgess, R.
    Ahfock, A.
    [J]. IET GENERATION TRANSMISSION & DISTRIBUTION, 2011, 5 (07) : 703 - 711
  • [2] Ding Wanglin, 2007, Automation of Electric Power Systems, V31, P74
  • [3] Principle and Control Design of a Novel Hybrid Arc Suppression Device in Distribution Networks
    Fan, Bishuang
    Yao, Ganzhou
    Wang, Wen
    Zeng, Xiangjun
    Guerrero, Josep M.
    Yu, Kun
    Zhuo, Chao
    [J]. IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2022, 69 (01) : 41 - 51
  • [4] Principle of Flexible Ground-Fault Arc Suppression Device Based on Zero-Sequence Voltage Regulation
    Fan, Bishuang
    Yao, Ganzhou
    Yu, Kun
    Zeng, Xiangjun
    Wang, Wen
    Zhuo, Chao
    Guerrero, Josep M.
    [J]. IEEE ACCESS, 2021, 9 : 2382 - 2389
  • [5] Stator-Ground Fault Location Method Based on Third-Harmonic Measures in High-Impedance Grounded Generators
    Friedemann, Daniel F.
    Motter, Daniel
    Oliveira, Robson A.
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2021, 36 (02) : 794 - 802
  • [6] Ground-fault currents in unit-connected generators with different elements grounding neutral
    Fulczyk, M
    Bertsch, J
    [J]. IEEE TRANSACTIONS ON ENERGY CONVERSION, 2002, 17 (01) : 61 - 66
  • [7] NEW-ENGLAND-ELECTRICS 39 YEARS OF EXPERIENCE WITH RESONANT NEUTRAL GROUNDING OF UNIT - CONNECTED GENERATORS
    GULACHENSKI, EM
    COURVILLE, EW
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 1991, 6 (03) : 1016 - 1024
  • [8] [贾文超 Jia Wenchao], 2022, [电力自动化设备, Electric Power Automation Equipment], V42, P79
  • [9] Stator fault damage considerations for generators on solidly grounded systems
    Powell, LJ
    [J]. IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2001, 37 (01) : 218 - 222
  • [10] Rifaat RM, 2000, IEEE IND APPLIC SOC, P3254, DOI 10.1109/IAS.2000.882632