Study of the Influence of Test Methods on DC Pollution Flashover Voltage of Insulator Strings and its Flashover Process

被引:40
|
作者
Zhang, Zhijin [1 ]
Jiang, Xinliang [1 ]
Sun, Caixin [1 ]
Hu, Jianlin [1 ]
Huang, Haizhou [1 ]
机构
[1] Chongqing Univ, State Key Lab Power Transmiss Equipment & Syst Se, Coll Elect Engn, Chongqing 400044, Peoples R China
关键词
DC transmission lines; pollution; flashover performance; insulator string; flashover process; COMPOSITE INSULATORS; AC FLASHOVER; MODEL; PERFORMANCE; PORCELAIN; ALTITUDE;
D O I
10.1109/TDEI.2010.5658230
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The influence of different test methods on dc pollution flashover voltage of insulator strings is presented in this paper. In addition, the relationship among the flashover voltages obtained by different voltage applied methods is put forward. Subsequently, the pollution flashover phenomenon is investigated using the insight from high-speed photography, and the comprehensive magnitude and orientation of forces on partial arcs is analyzed during the propagation. Thus, a new electrical circuit model consisting of a surface arc of length x(1) and air arc of length x(2) in series with a resistance representing the wet pollution layer supplied by a constant voltage is built. The results obtained from the model indicate that the main reason that makes the exponent b describing the influence of pollution on flashover voltage varying with the configuration and material of insulators is the difference of partial arc fluttering degree for insulators.
引用
收藏
页码:1787 / 1795
页数:9
相关论文
共 45 条
  • [41] Study on the DC Flashover Performance of Various Types of Insulators With Fan-Shaped Nonuniform Pollution
    Zhang, Zhijin
    Zhang, Dongdong
    You, Jinwei
    Zhao, Jiayao
    Jiang, Xingliang
    Hu, Jianlin
    IEEE TRANSACTIONS ON POWER DELIVERY, 2015, 30 (04) : 1871 - 1879
  • [42] An Improved Pollution Testing Methodology for Polymeric Insulators: Analysis on Surface Coating and Flashover Voltage Under Solid Layer Test
    Pushpa Y.G.
    Nagaraju V.
    Gobinath G.
    Journal of The Institution of Engineers (India): Series B, 2019, 100 (01) : 1 - 8
  • [43] Modeling of DC Critical Flashover of Transmission Line Insulator Long String under Windward/Leeward Side non-Uniform Pollution Condition
    Zhang, Dongdong
    Ni Xijun
    Wang, Shuzheng
    2019 IEEE 3RD INTERNATIONAL CONFERENCE ON GREEN ENERGY AND APPLICATIONS (ICGEA 2019), 2019, : 6 - 10
  • [44] CaSO4 Content in Contamination Influence on AC Pollution Flashover Characteristics of XWP2-160 Porcelain Insulator String
    Huang, Daochun
    Lu, Wei
    Deng, Yongqing
    Ruan, Jiangjun
    Xiong, Ziteng
    2018 IEEE INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND APPLICATION (ICHVE), 2018,
  • [45] Influence of Single and Multiple Dry Bands on Critical Flashover Voltage of Silicone Rubber Outdoor Insulators: Simulation and Experimental Study
    Arshad
    Mughal, Muhammad Ali
    Nekahi, Azam
    Khan, Mansoor
    Umer, Farhana
    ENERGIES, 2018, 11 (06)