FIELD MEASUREMENT AND NUMERICAL STUDY OF EXTERNAL WIND PRESSURE OF RIBBED COOLING TOWER

被引:0
作者
Yuanl, Yi-chen [1 ]
Yuan, Zi-hou [2 ,4 ]
Chen, Ming-xiang [3 ]
机构
[1] Huazhong Univ Sci & Technol, Sch Civil & Hydraul Engn, Wuhan 430070, Hubei, Peoples R China
[2] Wuhan Text Univ, Hubei Key Lab Digital Text Equipment, Wuhan 430073, Hubei, Peoples R China
[3] Wuhan Univ, Sch Civil Engn, Wuhan 430072, Hubei, Peoples R China
[4] Southeast Univ, Key Lab Concrete & Prestressed Concrete Struct, Minist Educ, Nanjing 211189, Jiangsu, Peoples R China
来源
CIVIL ENGINEERING JOURNAL-STAVEBNI OBZOR | 2021年 / 30卷 / 04期
基金
美国国家科学基金会;
关键词
Ribbed cooling tower; Wind pressure coefficient; Field measurement; Code; Reynolds number; SIMULATION; EXTREME; LOADS;
D O I
10.14311/CEJ.2021.04.0065
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
The hyperbolic thin-shell cooling tower is a typical wind-sensitive structure, and the full-size measurement is the most direct and important way to study the distribution of wind pressure on the surface of the cooling tower. But due to the limitations of engineering conditions and meteorological conditions, the field measured data are relatively lacking, and the field test data of ribbed cooling towers are less. In order to analyze the wind pressure distribution on the surface of the cooling tower, we chose a ribbed cooling tower in Toksun County, Xinjiang, China, where there is strong wind all year round, and field measurements were carried out to understand the wind load characteristics of the tower under the perennial dominant wind direction and the maximum wind direction. It is found that the absolute value of the negative pressure on the leeward side is larger than that in the code and the fluctuating wind pressure coefficient fluctuates greatly when the field measured wind speed is greater than 10m/s (15 meters above the ground). And for circular section cooling tower, the Reynolds number (Re) has great influence on wind pressure. With the increase of Re, the absolute value of the average negative pressure of the tail wind pressure coefficient increases, which should be paid attention to in design. Meanwhile, the regression curves of the average wind pressure coefficients measured on site under several typical working conditions are given by using the least square method, and its form is consistent with the standard (but the coefficients are different). Finally, Fluent software is used to calculate the external wind pressure of the cooling tower, and the variation law of numerical calculation is consistent with that of the field measured results, the Chinese code and German code.
引用
收藏
页码:847 / 859
页数:13
相关论文
共 24 条
[11]   Extreme Wind Pressures and Non-Gaussian Characteristics for Super-Large Hyperbolic Cooling Towers Considering Aeroelastic Effect [J].
Ke, Shitang ;
Ge, Yaojun .
JOURNAL OF ENGINEERING MECHANICS, 2015, 141 (07) :04015010
[12]  
Ministry of Construction of PRC, 2012, GB500092012 MIN CONS
[13]  
Ministry of Construction of PRC, 2014, GBT501022014 MIN CON
[14]  
NIEMANN HJ, 1976, J IND AERODYNAM, V1, P349
[15]   Nonlinear behavior and ultimate load bearing capacity of reinforced concrete natural draught cooling tower shell [J].
Noh, HC .
ENGINEERING STRUCTURES, 2006, 28 (03) :399-410
[16]   Wind-induced interference effects on two adjacent cooling towers [J].
Orlando, M .
ENGINEERING STRUCTURES, 2001, 23 (08) :979-992
[17]  
Sollenberger N J, 1974, P S FULLSC MEAS WIND
[18]  
SUN TF, 1992, J WIND ENG IND AEROD, V43, P2213
[19]  
Sun Tianfeng, 1983, ACTA AERODYNAMICA SI, V4
[20]   Research on non-stationary wind-induced effects and the working mechanism of full scale super-large cooling tower based on field measurement [J].
Wang, H. ;
Ke, S. T. ;
Ge, Y. J. .
JOURNAL OF WIND ENGINEERING AND INDUSTRIAL AERODYNAMICS, 2019, 184 :61-76