Experimental Study on Burning Characteristics of the Large-Scale Transformer Oil Pool Fire with Different Extinguishing Methods

被引:17
|
作者
Wu, Chuanping [1 ,2 ]
Zhou, Tiannian [1 ,2 ]
Chen, Baohui [1 ,2 ]
Liu, Yu [1 ,2 ]
Liang, Ping [1 ,2 ]
机构
[1] State Key Lab Disaster Prevent & Reduct Power Gri, Changsha 410007, Hunan, Peoples R China
[2] State Grid Hunan Elect Co Ltd Disaster Prevent &, Changsha 410007, Hunan, Peoples R China
关键词
Pool fire; Transformer oil; Extinguishing; Burning characteristics; Movable extinguishment platform; BEHAVIOR; BOILOVER;
D O I
10.1007/s10694-020-01012-x
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
In this study, a 100 m(2)steel tank was used to simulate transformer oil fires, with an aim of investigating the burning characteristics of a large-scale pool fire. To recover a real thermal state of transformer oil in operation, a heating system was employed to raise the initial fuel temperature. In total, three fire-extinguishing tests were performed using two delivery methods, i.e., a hand-held fire water branch (FWB) and fire water monitor (FWM) to understand their performance in fighting large-scale pool fires. The extinguishing activities using the FWB method were conducted by four trained firefighters, and the FWM was operated by a trained firefighter. Also, a sequence of bench-scale tests was conducted to investigate the impact of initial fuel temperature on the mass burning rate of transformer oil pool fires. This part is a supplement to the large-scale tests. The results demonstrated that the temperatures adjacent to the tank border were reduced as the vertical height increased. The growth rate of the flame height was enhanced in the development stage when the initial fuel temperature was pre-heated to a higher value. Meanwhile, it was found that the burning rate of transformer oil pool fire occurred a slight increase with the initial fuel temperature was grown according to the bench-scale data, while the impact of initial temperature was limited within the tested temperature range. In addition, it was shown that the FWB and FWM were both effective for fighting a large-scale transformer oil pool fire. However, their efficiency was influenced significantly by the concentration of the extinguishing agents and the application density of delivery. In contrast, the FWM might be a good choice when considering the safety of firefighters, because its delivery range is greater and extinguishing time is shorter as compared to the FWB. Here, it shall be noted that the FWM has also its flipsides. Sometimes, the application of a single FWM is not well to extinguish the corner fire or other fire types, in such cases, the FWM strategy should be to use two or more fire trucks in order to cover the whole accident pool.
引用
收藏
页码:461 / 481
页数:21
相关论文
共 50 条
  • [1] Experimental Study on Burning Characteristics of the Large-Scale Transformer Oil Pool Fire with Different Extinguishing Methods
    Chuanping Wu
    Tiannian Zhou
    Baohui Chen
    Yu Liu
    Ping Liang
    Fire Technology, 2021, 57 : 461 - 481
  • [2] Experimental study of burning rate in large-scale rectangular pool fire
    Jiang, Chunming
    Li, Yuntao
    Huang, Hong
    Zhao, Jinlong
    Wang, Zheng
    Zhang, Jianzhong
    JOURNAL OF FIRE SCIENCES, 2016, 34 (04) : 323 - 334
  • [3] Burning process and fire characteristics of transformer oil: A study focusing on the effects of oil type
    Zhang, Bosi
    Zhang, Jiaqing
    Huang, Yong
    Wang, Qing
    Yu, Zhihong
    Fan, Minghao
    JOURNAL OF THERMAL ANALYSIS AND CALORIMETRY, 2020, 139 (03) : 1839 - 1848
  • [4] Experimental study of burning behavior of large-scale crude oil fires in ice cavities
    Shi, X.
    Bellino, P. W.
    Simeoni, A.
    Rangwala, A. S.
    FIRE SAFETY JOURNAL, 2016, 79 : 91 - 99
  • [5] EXPERIMENTAL STUDY ON BURNING BEHAVIOR OF CRUDE KARANJA OIL POOL FIRE
    Chaudhary, Avinash
    Tiwari, Mahesh Kumar
    Gupta, Akhilesh
    Kumar, Surendra
    HEAT TRANSFER RESEARCH, 2021, 52 (14) : 25 - 45
  • [6] Experimental study on flow characteristics of a large-scale open jet wind tunnel for outdoor pool fire research
    Lei, Jiao
    Huang, Pengcheng
    Zhang, Linhe
    Yuan, Yukui
    Deng, Wenyang
    Mao, Shaohua
    Zhang, Jun
    JOURNAL OF WIND ENGINEERING AND INDUSTRIAL AERODYNAMICS, 2021, 210 (210)
  • [7] Experimental Study on the Fire-Spreading Characteristics and Heat Release Rates of Burning Vehicles Using a Large-Scale Calorimeter
    Park, Younggi
    Ryu, Jaiyoung
    Ryou, Hong Sun
    ENERGIES, 2019, 12 (08)
  • [8] Experimental Study on Horizontal Fire Spread Characteristics of Transformer Oil
    Li, Liyang
    Guo, Xincheng
    Lu, Rongsheng
    Chen, Peng
    Shi, Congling
    JOURNAL OF ENERGY RESOURCES TECHNOLOGY-TRANSACTIONS OF THE ASME, 2022, 144 (01):
  • [9] Experimental investigation at reduced scale of the effect of a ceiling on the burning rate of a pool fire
    Pretrel, Hugues
    Georges, Emeline
    Lefaux, Nicolas
    Suard, Sylvain
    Varrall, Kevin
    Vauquelin, Olivier
    JOURNAL OF FIRE SCIENCES, 2025, 43 (01) : 18 - 32
  • [10] Burning process and fire characteristics of transformer oilA study focusing on the effects of oil type
    Bosi Zhang
    Jiaqing Zhang
    Yong Huang
    Qing Wang
    Zhihong Yu
    Minghao Fan
    Journal of Thermal Analysis and Calorimetry, 2020, 139 : 1839 - 1848