Energy performance analysis and optimization of a coupled adsorption and absorption cascade refrigeration system

被引:31
作者
Chen, W. D. [1 ]
Chua, K. J. [1 ]
机构
[1] Natl Univ Singapore, Dept Mech Engn, 9 Engn Dr 1, Singapore 117576, Singapore
基金
新加坡国家研究基金会;
关键词
Low-grade waste heat recovery; Energy cascade utilization; Adsorption chiller; Energy optimization; Combined cooling and power system; WASTE HEAT; OPTIMAL-DESIGN; RECOVERY; CHILLER; EXERGY; IMPROVEMENT; SIMULATION; SELECTION; STRATEGY; CCHP;
D O I
10.1016/j.apenergy.2021.117518
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
An energy cascade utilization system is an advanced technology that recoveries waste heat energy efficiently. However, research on cascade systems by utilizing waste hot water with 60-100.C is still considerably lacking in the literature. Specifically, this paper investigates the waste heat recovery performance of a multistage coupled absorption chiller (ABC)-adsorption chiller (ADC) cascade system. The proposed ABC-ADC cascade system is capable of producing potable water and three streams of chilled water under different temperature settings. Firstly, the experimental analysis is judiciously carried out on a four-bed two-evaporator ADC subsystem prototype. Key results reveal that the ADC's maximum specific daily water production is 10.5 m(3)/day/ton. Subsequently, the ABC-ADC cascade system's performance is experimentally analysed and optimized. The achievable maximum cooling coefficient of performance (COPc) is obtained to be 0.55. Additionally, a general method is proposed to optimize the subsystem's cooling capacity combination of the ABC-ADC cascade system in search of an optimal COPc. The results indicate that the optimized COPc can further be enhanced by around 20%. The performance efficiency of an optimized ABC-ADC cascade system incorporating a microturbine system is then investigated. Compared to the experimental ABC-ADC cascade system, the optimized system' total coefficient of performance is demonstrated to improve by 18%. The primary energy saving ratio is also promoted from 9.8% to 18%. Moreover, 68.92% of the gas turbine's dissipated energy is able to be recovered by the optimized ABC-ADC system. As far as application is concerned, this cascade system has been demonstrated to be superior to standalone heat-driven chillers with great commercial potential for implementation in industries where low-grade waste heat is readily available.
引用
收藏
页数:24
相关论文
共 50 条
[1]   Comparison of some recent numerical methods for initial-value problems for stiff ordinary differential equations [J].
Abelman, Shirley ;
Patidar, Kailash C. .
COMPUTERS & MATHEMATICS WITH APPLICATIONS, 2008, 55 (04) :733-744
[2]   Optimal design, operation and analytical criteria for determining optimal operating modes of a CCHP with fired HRSG, boiler, electric chiller and absorption chiller [J].
Afzali, Sayyed Faridoddin ;
Mahalec, Vladimir .
ENERGY, 2017, 139 :1052-1065
[3]   Review of tri-generation technologies: Design evaluation, optimization, decision-making, and selection approach [J].
Al Moussawi, Houssein ;
Fardoun, Farouk ;
Louahlia-Gualous, Hasna .
ENERGY CONVERSION AND MANAGEMENT, 2016, 120 :157-196
[4]   Energy consumption and water production cost of conventional and renewable-energy-powered desalination processes [J].
Al-Karaghouli, Ali ;
Kazmerski, Lawrence L. .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2013, 24 :343-356
[5]   Comprehensive strategies for performance improvement of adsorption air conditioning systems: A review [J].
Alahmer, Ali ;
Ajib, Salman ;
Wang, Xiaolin .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2019, 99 :138-158
[6]  
American Society of Heating R and A-CE Knovel (Firm), 2009, ASHRAE HDB FUND INCH
[7]   Exergy efficiency analysis in buildings climatized with LiCl-H2O solar cooling systems that use swimming pools as heat sinks [J].
Borge, D. ;
Colmenar, A. ;
Castro, M. ;
Martin, S. ;
Sancristobal, E. .
ENERGY AND BUILDINGS, 2011, 43 (11) :3161-3172
[8]   Energy- and exergy-based working fluid selection and performance analysis of a high-temperature PEMFC-based micro combined cooling heating and power system [J].
Chang, Huawei ;
Wan, Zhongmin ;
Zheng, Yao ;
Chen, Xi ;
Shu, Shuiming ;
Tu, Zhengkai ;
Chan, Siew Hwa ;
Chen, Rui ;
Wang, Xiaodong .
APPLIED ENERGY, 2017, 204 :446-458
[9]   Parameter analysis and energy optimization of a four-bed, two-evaporator adsorption system [J].
Chen, W. D. ;
Chua, K. J. .
APPLIED ENERGY, 2020, 265 (265)
[10]   Proposal and analysis of a novel heat-driven absorption-compression refrigeration system at low temperatures [J].
Chen, Yi ;
Han, Wei ;
Jin, Hongguang .
APPLIED ENERGY, 2017, 185 :2106-2116