Implementation, Comparison and Application of an Average Simulation Model of a Wind Turbine Driven Doubly Fed Induction Generator

被引:9
作者
Arachchige, Lidula N. Widanagama [1 ]
Rajapakse, Athula D. [2 ]
Muthumuni, Dharshana [3 ]
机构
[1] Univ Moratuwa, Dept Elect Engn, Moratuwa 10400, Sri Lanka
[2] Univ Manitoba, Dept Elect & Comp Engn, Winnipeg, MB R3T 5V6, Canada
[3] Manitoba HVDC Res Ctr, Winnipeg, MB R3P 1A3, Canada
关键词
average simulation model; doubly-fed induction generator; DFIG model; electromagnetic transients; wind turbine; MICROGRIDS;
D O I
10.3390/en10111726
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Wind turbine driven doubly-fed induction generators (DFIGs) are widely used in the wind power industry. With the increasing penetration of wind farms, analysis of their effect on power systems has become a critical requirement. This paper presents the modeling of wind turbine driven DFIGs using the conventional vector controls in a detailed model of a DFIG that represents power electronics (PE) converters with device level models and proposes an average model eliminating the PE converters. The PSCAD/EMTDC (TM) (4.6) electromagnetic transient simulation software is used to develop the detailed and the proposing average model of a DFIG. The comparison of the two models reveals that the designed average DFIG model is adequate for simulating and analyzing most of the transient conditions.
引用
收藏
页数:25
相关论文
共 21 条
[1]  
[Anonymous], GLOB WIND REP
[2]  
[Anonymous], 2009, P 2009 IEEE POW EN S
[3]  
CanWEA (Canadian Wind Energy Association), 2016, POW CAN FUT
[4]   Dynamic modeling of doubly fed induction generator wind turbines [J].
Ekanayake, JB ;
Holdsworth, L ;
Wu, XG ;
Jenkins, N .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2003, 18 (02) :803-809
[5]  
Hosseini SH, 2005, ICEMS 2005: PROCEEDINGS OF THE EIGHTH INTERNATIONAL CONFERENCE ON ELECTRICAL MACHINES AND SYSTEMS, VOLS 1-3, P1261
[6]   Subsynchronous Resonance Mitigation for Series-Compensated DFIG-Based Wind Farm by Using Two-Degree-of-Freedom Control Strategy [J].
Huang, Po-Hsu ;
El Moursi, Mohamed Shawky ;
Xiao, Weidong ;
Kirtley, James L., Jr. .
IEEE TRANSACTIONS ON POWER SYSTEMS, 2015, 30 (03) :1442-1454
[7]  
Hydro M., 2010, TECHNICAL REQUIREMEN
[8]  
Javan E., 2011, P 2 POW EL DRIV SYST
[9]   Overview of different wind generator systems and their comparisons [J].
Li, H. ;
Chen, Z. .
IET RENEWABLE POWER GENERATION, 2008, 2 (02) :123-138
[10]   Voltage balancing and synchronization of microgrids with highly unbalanced loads [J].
Lidula, N. W. A. ;
Rajapakse, A. D. .
RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2014, 31 :907-920