Seismic retrofitting of an HV circuit breaker using base isolation with wire ropes. Part 2: Shaking-table test validation

被引:58
作者
Alessandri, S. [1 ]
Giannini, R. [1 ]
Paolacci, F. [1 ]
Amoretti, M. [2 ]
Freddo, A. [2 ]
机构
[1] Roma Tre Univ, Rome, Italy
[2] Tema Rete Italia, Sviluppo Rete Ingn, Rome, Italy
关键词
HV equipment; Circuit breaker; Seismic isolation; Wire rope isolators; VOLTAGE DISCONNECT SWITCH; PERFORMANCE EVALUATION;
D O I
10.1016/j.engstruct.2015.03.031
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
This paper addresses the experimental characterisation of a base-isolation system for the seismic qualification, of High Voltage (HV) ceramic circuit breakers, in accordance with the European standard CEI EN 62271-207. The adopted solution is based on an innovative application of wire rope isolators. The results of a preliminary investigation of an HV circuit breaker, which was base-isolated with wire ropes, were previously illustrated in a companion paper in which the effectiveness of this isolation system was analytically demonstrated. To validate these results, a shake table test campaign has been performed that includes the performance analysis of two optimal isolation system configurations. The results, which are illustrated in this paper, show both the effectiveness of this isolation system and the reliability of the proposed FE model. (C) 2015 Elsevier Ltd. All rights reserved.
引用
收藏
页码:263 / 274
页数:12
相关论文
共 23 条
[1]   Seismic retrofitting of an HV circuit breaker using base isolation with wire ropes. Part 1: Preliminary tests and analyses [J].
Alessandri, S. ;
Giannini, R. ;
Paolacci, F. ;
Malena, M. .
ENGINEERING STRUCTURES, 2015, 98 :251-262
[2]  
[Anonymous], 2008, 62271207 CEI EN
[3]  
Bonacina G, 1995, 10 EUR C EARTHQ ENG
[4]  
Colombo E, 1995, INT WORKSH RISK REL
[5]  
Di Donna M., 2002, 12 EUR C EARTHQ ENG
[6]  
Ersoy S., 2001, Earthquake Spectra, V17, P569, DOI [10.1193/1.1423653, DOI 10.1193/1.1423653]
[7]  
Gasparini D.A., 1976, SIMQKE PROGRAM ARTIF
[8]  
Gilani A.S., 1999, SEISMIC EVALUATION R
[9]  
Gilani ASJ, 2000, 200006 PEER U CAL BE
[10]   Seismic performance evaluation of high-voltage disconnect switches using real-time hybrid simulation: II. Parametric study [J].
Guenay, Selim ;
Mosalam, Khalid M. .
EARTHQUAKE ENGINEERING & STRUCTURAL DYNAMICS, 2014, 43 (08) :1223-1237