Location Method for Interline and Grounded Faults of Double-Circuit Transmission Lines Based on Distributed Parameters
被引:30
作者:
Ma, Jing
[1
,2
]
Shi, Yuxin
[3
]
Ma, Wei
[1
]
Wang, Zengping
[1
]
机构:
[1] North China Elect Power Univ, State Key Lab Alternate Elect Power Syst Renewabl, Beijing 071003, Peoples R China
[2] Virginia Polytech Inst & State Univ, Bradley Dept Elect & Comp Engn, Blacksburg, VA 24061 USA
[3] Shanxi Elect Power Corp, Elect Power Res Inst, Taiyuan 030000, Shanxi, Peoples R China
基金:
中国国家自然科学基金;
关键词:
Distributed parameters;
double-circuit transmission line;
fault-location function;
interline fault;
UNSYNCHRONIZED MEASUREMENTS;
ALGORITHM;
D O I:
10.1109/TPWRD.2014.2360076
中图分类号:
TM [电工技术];
TN [电子技术、通信技术];
学科分类号:
0808 ;
0809 ;
摘要:
This paper presents a one-terminal fault-location method for interline and grounded faults of double-circuit transmission lines considering the distributed parameter. The influence of mutual inductances is taken into account in a six-sequence network of a distributed parameter model. And the compensation voltage with the help of a co-rotating zero-sequence compensation coefficient and reverse zero-sequence compensation coefficient is defined. Then, the phase and the amplitude of fault voltage are calculated by utilizing the relationship between measured reverse sequence current and fault reverse sequence current. Then, fault-location function is constructed by utilizing the measured voltage, measured current, and estimated fault voltage. Finally, the fault location is identified by solving the phase mutation point of fault-location function. The simulation results show that the method can be widely used for interline and grounded faults without the information of other substations. In addition, this method is merely influenced by fault location, transition resistance, source impedance, and is able to locate the fault accurately and is easy to implement.
引用
收藏
页码:1307 / 1316
页数:10
相关论文