Protection of Double-circuit Transmission Line Using Superimposed Current

被引:12
作者
Bhalja, B. [1 ]
Purohit, Swati [2 ]
机构
[1] GIDC, AD Patel Inst Technol, Dept Elect Engn, Anand 388121, Gujarat, India
[2] Govt Engn Coll, Dept Elect Engn, Rajkot, Gujarat, India
关键词
superimposed currents; double circuit transmission line; cross differential relay; ADAPTIVE DISTANCE PROTECTION; NON-COMMUNICATION PROTECTION; DIFFERENTIAL PROTECTION; SCHEME;
D O I
10.1080/15325008.2010.528545
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This article presents a differential protection scheme for a double-circuit transmission line using a superimposed component of current. The proposed scheme is based on the ratio of directional current difference setting value to directional current bias setting value of the respective phase at both ends. These two quantities are derived based on the difference and the summation of the superimposed currents of the respective phase. The proposed scheme provides proper discrimination between in-zone faults and out-of-zone faults during complete loss of generation at one of the buses. Further, it is highly sensitive toward high-resistance faults and provides instantaneous operation to the entire line. Moreover, the relay provides reliability and selectivity for discriminating cross-country faults and internal faults and remains stable against external faults. The proposed scheme has been tested under different fault conditions with varying fault resistance between 0-200 . A series of tests using test signals generated by PSCAD/EMTDC (Manitoba HVDC Research Centre Inc., Winnipeg, Manitoba, Canada) on realistic data of a part of the Indian 400-kV power transmission system network have proved the accuracy and effectiveness of the proposed scheme.
引用
收藏
页码:590 / 604
页数:15
相关论文
共 20 条
[1]  
[Anonymous], P INT C COMP VIS BEI
[2]  
Benmouyal G., 1999, SUPERIMPOSED QUANTIT, P1
[3]   New differential protection scheme for tapped transmission line [J].
Bhalja, B. ;
Maheshwari, R. P. .
IET GENERATION TRANSMISSION & DISTRIBUTION, 2008, 2 (02) :271-279
[4]   Trends in adaptive distance protection of multiterminal and double-circuit lines [J].
Bhalja, B ;
Maheshwari, RP .
ELECTRIC POWER COMPONENTS AND SYSTEMS, 2006, 34 (06) :603-617
[5]   Protection of transmission line paralleled along the same right-of-way [J].
Bhalja, Bhavesh ;
Maheshwari, R. P. .
ELECTRIC POWER COMPONENTS AND SYSTEMS, 2008, 36 (03) :239-249
[6]   Percentage differential protection of double-circuit line using wavelet transform [J].
Bhalja, Bhavesh ;
Maheshwari, R. P. .
ELECTRIC POWER COMPONENTS AND SYSTEMS, 2007, 35 (08) :945-954
[7]   An adaptive distance relaying scheme using radial basis function neural network [J].
Bhalja, Bhavesh ;
Maheshwari, R. P. .
ELECTRIC POWER COMPONENTS AND SYSTEMS, 2007, 35 (03) :245-259
[8]   A New Digital Relaying Scheme for Parallel Transmission Line [J].
Bhalja, Bhavesh ;
Maheshwari, Rudra Prakash ;
Parikh, Urmil B. .
INTERNATIONAL JOURNAL OF EMERGING ELECTRIC POWER SYSTEMS, 2009, 10 (03)
[9]   High-resistance faults on two terminal parallel transmission line: Analysis, simulation studies, and an adaptive distance relaying scheme [J].
Bhalja, Bhavesh R. ;
Maheshwari, Rudra Prakash .
IEEE TRANSACTIONS ON POWER DELIVERY, 2007, 22 (02) :801-812
[10]   Adaptive non-communication protection for power lines BO scheme 2 - The instant operation approach [J].
Bo, ZQQ .
IEEE TRANSACTIONS ON POWER DELIVERY, 2002, 17 (01) :92-96