SIMULATION OF THE IMPACT OF AQUIFERS ON THE GROUND TEMPERATURE IN GROUND-SOURCE HEAT PUMP OPERATION

被引:0
|
作者
Capozza, Antonio [1 ]
Zarrella, Angelo [2 ]
机构
[1] RSE SpA Ric Sistema Energet, Power Syst Dev Dept, Milan, Italy
[2] Univ Padua, Dept Ind Engn, Padua, Italy
来源
BUILDING SIMULATION 2013: 13TH INTERNATIONAL CONFERENCE OF THE INTERNATIONAL BUILDING PERFORMANCE SIMULATION ASSOCIATION | 2013年
关键词
EXCHANGERS; ADVECTION;
D O I
暂无
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
The winter operation of ground-source heat pumps is expected to lead to drift phenomena in the zones surrounding the vertical ground heat exchangers. A moving aquifer tends to oppose the thermal drift, due to the advection groundwater phenomena. A modelling study of the quantitative influence of the groundwater flow on the thermal drift is performed, based on the moving infinite line source model. The analytical solution of this model is numerically solved and implemented in a computer software. Referring to a particularly critical case study, an easy-to-use application of the model based on this analytical solution is then presented. The influence of the existing flow is assessed upon either improving the effective operating conditions of the heat pump plant or reducing of the total borehole length.
引用
收藏
页码:1322 / 1329
页数:8
相关论文
共 50 条
  • [1] Investigations on the influence of aquifers on the ground temperature in ground-source heat pump operation
    Capozza, Antonio
    De Carli, Michele
    Zarrella, Angelo
    APPLIED ENERGY, 2013, 107 : 350 - 363
  • [2] Study on ground temperature response of multilayer stratums under operation of ground-source heat pump
    Zhou, Shiyu
    Cui, Wenzhi
    Tao, Jiaxiang
    Peng, Qingyuan
    APPLIED THERMAL ENGINEERING, 2016, 101 : 173 - 182
  • [3] Simulation Tool for Ground-Source Heat Pump System with Multiple Ground Heat Exchangers
    Katsura, Tako
    Nagano, Katsunori
    ASHRAE TRANSACTIONS 2018, VOL 124, PT 2, 2018, 124 : 92 - 101
  • [4] Impact of weather variation on ground-source heat pump design
    Pertzborn, Amanda
    Nellis, Greg
    Klein, Sanford
    HVAC&R RESEARCH, 2011, 17 (02): : 174 - 185
  • [5] GROUND-SOURCE HEAT-PUMP SYSTEMS
    CALM, J
    ASHRAE JOURNAL-AMERICAN SOCIETY OF HEATING REFRIGERATING AND AIR-CONDITIONING ENGINEERS, 1983, 25 (05): : 59 - 59
  • [6] Analysis of geo-temperature recovery under intermittent operation of ground-source heat pump
    Shang, Yan
    Li, Sufen
    Li, Haijun
    ENERGY AND BUILDINGS, 2011, 43 (04) : 935 - 943
  • [7] Numerical Simulation of Solar Ground-Source Heat Pump with Latent Heat Storage
    Wang, Fang
    Liu, Zhilong
    Li, Zhongjian
    Zheng, Maoyu
    MATERIALS AND MANUFACTURING TECHNOLOGY, PTS 1 AND 2, 2010, 129-131 : 1069 - +
  • [8] Analysis of Groundwater Advection and Ground-Heat Exchanger Spacing on Intermittent Ground-Source Heat Pump Operation
    Lines, Scott Harold
    Llano-Serna, Marcelo A.
    Williams, David J.
    ENERGY GEOTECHNICS, SEG-2018, 2019, : 19 - 26
  • [9] Analysis of the operation performance of a hybrid solar ground-source heat pump system
    Zhang, Xueyou
    Wang, Enyu
    Liu, Liansheng
    Qi, Chengying
    Zhen, Jinyu
    Meng, Ying
    ENERGY AND BUILDINGS, 2022, 268
  • [10] APPLICATION OF THE GROUND-SOURCE HEAT PUMP SYSTEMS IN CHINA
    Yang, Wei
    Zhou, Jin
    Xu, Wei
    Zhang, Guoqiang
    FIFTH INTERNATIONAL WORKSHOP ON ENERGY AND ENVIRONMENT OF RESIDENTIAL BUILDINGS AND THIRD INTERNATIONAL CONFERENCE ON BUILT ENVIRONMENT AND PUBLIC HEALTH, VOL I AND II, PROCEEDINGS, 2009, : 1836 - 1843