A current-based solution for transformer differential protection -: Part I:: Problem statement

被引:108
作者
Guzmán, A [1 ]
Zocholl, S
Benmouyal, G
Altuve, HJ
机构
[1] Schweitzer Engn Labs, Pullman, WA USA
[2] Univ Autonoma Nuevo Leon, Monterrey, NL, Mexico
关键词
differential protection; power transformer protection; protective relaying;
D O I
10.1109/61.956726
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper analyzes the problem of transformer differential protection. First, we review the concept of transformer differential protection. We then analyze magnetizing inrush, overexcitation, and current transformer (CT) saturation phenomena as possible causes of relay misoperation. Finally, we summarize the existing methods for discriminating internal faults from inrush and overexcitation conditions. In Part II of the paper, we propose a new approach for transformer differential protection and describe the relay that is based on this approach.
引用
收藏
页码:485 / 491
页数:7
相关论文
共 32 条
[1]  
Atabekov G.I., 1960, RELAY PROTECTION HIG
[2]  
Berdy J., 1976, S TRANSF EXC INR CHA
[3]  
BERTULA G, 1945, BROWN BOVERI REV, V32, P129
[4]  
Cordray R. E., 1931, ELECTR ENG, V50, P361, DOI [10.1109/EE.1931.6430259, DOI 10.1109/EE.1931.6430259]
[5]  
CORDRAY RE, 1931, ELECT WORLD 0725, P160
[6]  
Dmitrenko A. M., 1970, Izvestiya Vysshikh Uchebnykh Zavedenii, Elektromekhanika, P335
[7]  
Dmitrenko A. M., 1979, Elektrichestvo, P55
[8]  
EDGELEY RK, 1952, IEE P 2, V99, P297
[9]   3-PHASE DIFFERENTIAL RELAY FOR TRANSFORMER PROTECTION [J].
EINVALL, CH ;
LINDERS, JR .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1975, 94 (06) :1971-1980
[10]  
Giuliante A, 1991, P GEORG TECH PROT RE, P1