Experimental performance evaluation of a closed-loop vertical ground source heat pump in the heating mode using energy analysis method

被引:38
作者
Kara, Yusuf Ali [1 ]
机构
[1] Ataturk Univ, Fac Engn, Dept Mech Engn, TR-25240 Erzurum, Turkey
关键词
ground source heat pump; ground heat exchanger; vertical borehole; coefficient of performance; heat pumps; COP; THERMAL PERFORMANCE; SYSTEM; TURKEY;
D O I
10.1002/er.1316
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
An experimental study is performed to determine the performance of a ground source heat pump (GSHP) system in the heating mode in the city of Erzurum, Turkey. The GSHP system using R-134a as refrigerant has a single U-tube ground heat exchanger (GHE) made of polyethylene pipe with a 16mm inside diameter. The GHE was placed in a vertical borehole with 55 in depth and 203.2 mm diameter. The average coefficients of performance (COP) of the GSHP system and heat pump in heating mode are calculated as 2.09 and 2.57, respectively. The heat extraction rate per meter of the borehole is determined as 33.60 Wm(-1). Considering the current gas and electric prices in Erzurum city, the equivalent COP of the GSHP system should be 2.92 for the same energy cost comparing with natural gas. The virgin ground in Erzurum basin has high permeability and low thermal conductivity. In order to improve the thermal efficiency of GHE and thus improve COP of a GSHP in the basin, the borehole should be backfilled with sand as low-cost backfill material and a 1 to 2 m thick surface plug of clay should be inserted. Copyright (C) 2007 John Wiley & Sons, Ltd.
引用
收藏
页码:1504 / 1516
页数:13
相关论文
共 18 条
[1]  
Bayraktutan MS, 1996, Q J ENG GEOL, V29, P209
[2]  
Cane D., 1998, ASHRAE T, V104, P677
[3]  
DAGSOZ AK, 1995, DEGREE DAYS CITIES T
[4]   Ground source heat pump - description and preliminary results of the Eco House system [J].
Doherty, PS ;
Al-Huthaill, S ;
Riffat, SB ;
Abodahab, N .
APPLIED THERMAL ENGINEERING, 2004, 24 (17-18) :2627-2641
[5]  
*ECMS, 2006, UNPUB REC WEATH DAT
[6]   Performance evaluation of a vertical ground-source heat pump system in Izmir, Turkey [J].
Hepbasli, A .
INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2002, 26 (13) :1121-1139
[7]   Experimental study of a closed loop vertical ground source heat pump system [J].
Hepbasli, A ;
Akdemir, O ;
Hancioglu, E .
ENERGY CONVERSION AND MANAGEMENT, 2003, 44 (04) :527-548
[8]  
Holman J.P., 1994, Experimental Methods for Engineers, P49
[9]   Experimental thermal performance evaluation of a horizontal ground-source heat pump system [J].
Inalli, M ;
Esen, H .
APPLIED THERMAL ENGINEERING, 2004, 24 (14-15) :2219-2232
[10]  
Kavanaugh S, 1997, GROUND SOURCE HEAT P, P167