Fault location in overhead transmission line: A novel non-contact measurement approach for traveling wave-based scheme

被引:12
作者
Anane, Paul Oswald Kwasi [1 ]
Huang, Qi [1 ]
Bamisile, Olusola [1 ]
Ayimbire, Patrick Nyaaba [1 ]
机构
[1] Univ Elect Sci & Technol China, Sch Mech & Elect Engn, Sichuan Prov Key Lab Power Syst Wide Area Measure, Chengdu 611731, Peoples R China
关键词
Non-contact measurement; Overhead transmission line; Traveling wave measurement; Magnetic Field sensor; Fault location; CURRENT SENSOR; ALGORITHM; IMPEDANCE;
D O I
10.1016/j.ijepes.2021.107233
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Traveling wave fault location methods have gained considerable growth over the years, with the anticipation that power systems will be accurate and reliable everywhere. But the performance of classical traveling wave methods has focused only on traditional current transformer measurement in the literature till date. Therefore, in this paper, an innovative non-contact measurement of traveling wave formulation is proposed to achieve accurate fault location and time of arrival detection on a two-terminal overhead transmission line, since power cable naturally generates magnetic and electrical fields in the surrounding atmosphere. The proposed method solitary depends on the first two and successive time differences between the incident and reflective wave from the fault point of the transmission line. Thus, the proposed scheme does not depend on current transformer measurement that stimulates the accuracy and reliability of the conventional traveling wave fault location method. To ensure an accurate time of arrival waves detection, we exploit the magnetic field sensor array on each tower to measure the quality of current traveling waves generated on the transmission line and locate the transient disturbances as a result of a short circuit. By analyzing the line energization, a comprehensive fault analysis on a 500-kV line was simulated with PSCAD/MATLAB toolbox compared to the two-terminal classical method. The sensitivity analysis demonstrated that the proposed method is much accurate and reliable to be deployed and cost-effective, making it highly useful and efficient in comparison to the classical two terminals traveling wave method with an average error of 0.014%. The effectiveness of the proposed method was verified by laboratory experimental setup.
引用
收藏
页数:11
相关论文
共 50 条
  • [21] A novel traveling wave fault location method for transmission network based on time linear dependence
    Yu, Kun
    Zeng, Jupeng
    Zeng, Xiangjun
    Liu, Feng
    Zu, Yarui
    Yu, Quan
    Zhuo, Chao
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2021, 126
  • [22] Study on T type Transmission Line Fault Location Based on Voltage Traveling Wave
    Li, Yongfu
    Fu, Jin
    Wang, Qian
    Peng, Huadong
    Ji, Yongliang
    Zhao, Hongbin
    Liu, Jinjun
    Zeng, Xianglong
    2016 IEEE INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND APPLICATION (ICHVE), 2016,
  • [23] Fault Location Scheme for Multi-Terminal Transmission Line Based on Frequency-Dependent Traveling Wave Velocity and Distance Matrix
    Zeng, Ruochen
    Zhang, Luliang
    Wu, Qing-Hua
    IEEE TRANSACTIONS ON POWER DELIVERY, 2023, 38 (06) : 3980 - 3990
  • [24] Traveling Wave-Based Fault Location on Two-Segment Hybrid Lines
    Leite, E. J. S., Jr.
    Lopes, F. V.
    Ribeiro, J. P. G.
    2018 IEEE POWER & ENERGY SOCIETY GENERAL MEETING (PESGM), 2018,
  • [25] A Traveling-Wave-based Fault Location Method in Transmission Line based on LMD and TEO
    Qian Hanbo
    Liu Hongbao
    Jia Huibin
    Zhang Guoyun
    PROCEEDINGS OF THE INTERNATIONAL CONFERENCE ON LOGISTICS, ENGINEERING, MANAGEMENT AND COMPUTER SCIENCE, 2014, 101 : 856 - 860
  • [26] Past, Present, and Future Trends of Traveling Wave-Based Fault Location Solutions
    Lopes, Felipe, V
    Reis, Raphael L. A.
    Silva, Kleber M.
    Martins-Britto, Amauri
    Ribeiro, Eduardo P. A.
    Moraes, Caio M.
    Rodrigues, Marco Antonio M.
    2021 WORKSHOP ON COMMUNICATION NETWORKS AND POWER SYSTEMS (WCNPS), 2021,
  • [27] Non-contact voltage measurement of three-phase overhead transmission line based on electric field inverse calculation
    Xiao, Dongping
    Xie, Yutong
    Ma, Qichao
    Zheng, Qi
    Zhang, Zhanlong
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2018, 12 (12) : 2952 - 2957
  • [28] DCVD-VMD Enabled Traveling Wave-Based Fault Location in Nonhomogenous AC Microgrids
    Jnaneswar, Kolli
    Rana, Ankur Singh
    Thomas, Mini Shaji
    IEEE SYSTEMS JOURNAL, 2023, 17 (02): : 2411 - 2421
  • [29] Traveling wave fault location for teed transmission line based on solutions of linear equations
    Wang, Z. (12121561@bjtu.edu.cn), 1600, Power System Technology Press (38): : 1046 - 1050
  • [30] Closed-Form Solution for Traveling Wave-Based Fault Location on Non-Homogeneous Lines
    Silva Leite, Eduardo Jorge, Jr.
    Lopes, Felipe V.
    Costa, Flavio Bezerra
    Araujo Neves, Washington Luiz
    IEEE TRANSACTIONS ON POWER DELIVERY, 2019, 34 (03) : 1138 - 1150