DFIG wind generation systems operating with limited converter rating considered under unbalanced network conditions - Analysis and control design

被引:59
作者
Hu, Jiabing [1 ,2 ]
He, Yikang [1 ]
机构
[1] Zhejiang Univ, Coll Elect Engn, Hangzhou 310027, Peoples R China
[2] Univ Sheffield, Dept Elect & Elect Engn, Sheffield S1 3JD, S Yorkshire, England
基金
中国国家自然科学基金;
关键词
Wind power; Doubly-fed induction generator (DFIG); Unbalanced network; Grid-side converter (GSC); Rotor-side converter (RSC); Proportional integral plus resonant (PI - R);
D O I
10.1016/j.renene.2010.07.004
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
This paper presents an analysis and operation of doubly-fed induction generator (DFIG)-based wind power generation systems under unbalanced network voltage conditions. The limited voltage and current ratings, and control capabilities of both grid side and rotor-side converters (GSC&RSC) for unbalanced network voltage compensation are investigated. A current control scheme consisting of a proportional integral (PI) controller plus a resonant (R) compensator is designed. The control scheme is implemented in the positive synchronous rotating reference frame and provides precise current control for both the GSC and RSC without involving the decomposition process of positive and negative sequence currents. By taking into account both the converters' current ratings, a coordinated control strategy between the GSC and RSC is proposed and adjusted. Finally, simulation studies on a 1.5 MW DFIG generation system and experimental tests on a 1.5 kW prototype are carried out. The correctness of the analytical results as well as the feasibility of the proposed coordinated control scheme are confirmed when the network voltage is unbalanced. (C) 2010 Elsevier Ltd. All rights reserved.
引用
收藏
页码:829 / 847
页数:19
相关论文
共 22 条
  • [1] Control of back-to-back PWM converters for DFIG wind turbine systems under unbalanced grid voltage
    Abo-Khalil, Ahmed G.
    Lee, Dong-Choon
    Jang, Jeong-Ik
    [J]. 2007 IEEE INTERNATIONAL SYMPOSIUM ON INDUSTRIAL ELECTRONICS, PROCEEDINGS, VOLS 1-8, 2007, : 2637 - +
  • [2] [Anonymous], 2005, INT C POW SYST TRANS
  • [3] HU J, 2009, ELECT POWER SYSTEM R, V2, P273
  • [4] HU J, 2006, J ZHEJIANG UNIV-SC A, V10, P1757
  • [5] Enhanced control of DFIG-used back-to-back PWM VSC under unbalanced grid voltage conditions
    Hu, Jia-Bing
    He, Yi-Kang
    Nian, Heng
    [J]. JOURNAL OF ZHEJIANG UNIVERSITY-SCIENCE A, 2007, 8 (08): : 1330 - 1339
  • [6] Reinforced Control and Operation of DFIG-Based Wind-Power-Generation System Under Unbalanced Grid Voltage Conditions
    Hu, Jiabing
    He, Yikang
    [J]. IEEE TRANSACTIONS ON ENERGY CONVERSION, 2009, 24 (04) : 905 - 915
  • [7] Improved Control of DFIG Systems During Network Unbalance Using PI-R Current Regulators
    Hu, Jiabing
    He, Yikang
    Xu, Lie
    Williams, Barry W.
    [J]. IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2009, 56 (02) : 439 - 451
  • [8] Idsoe Nass B, 2002, IEEE WORKSH WIND POW, P17
  • [9] Sensorless direct voltage control of the stand-alone slip-ring induction generator
    Iwanski, Grzegorz
    Koczara, Wlodzimierz
    [J]. IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2007, 54 (02) : 1237 - 1239
  • [10] Dynamic behavior of the doubly fed induction generator during three-phase voltage dips
    Lopez, Jesus
    Sanchis, Pablo
    Roboam, Xavier
    Marroyo, Luis
    [J]. IEEE TRANSACTIONS ON ENERGY CONVERSION, 2007, 22 (03) : 709 - 717