Real-time temperature predictions in IT server enclosures

被引:25
作者
Moazamigoodarzi, Hosein [1 ,2 ]
Pal, Souvik [1 ]
Ghosh, Suvojit [1 ]
Puri, Ishwar K. [1 ,2 ]
机构
[1] McMaster Univ, Comp Infrastruct Res Ctr, Hamilton, ON, Canada
[2] McMaster Univ, Dept Mech Engn, Hamilton, ON, Canada
基金
加拿大自然科学与工程研究理事会;
关键词
Rack mountable cooling units; Temperature prediction; Zonal method; Flowrate mismatch; Energy balance; PROPER ORTHOGONAL DECOMPOSITION; DATA CENTERS; ZONAL MODEL; AIR-FLOW; TECHNOLOGY; SIMULATION; SYSTEMS; POWER;
D O I
10.1016/j.ijheatmasstransfer.2018.08.091
中图分类号
O414.1 [热力学];
学科分类号
摘要
Current data center (DC) cooling architectures are inefficient due to (1) inherent airflow efficiencies and (2) their inability to spatiotemporally control cooling airflow and DC temperatures on demand. Rack-based cooling is a promising recent alternative since it provides more effective airflow distribution and is more amenable to rapid real-time control. A control scheme should be able to predict spatiotemporal temperature changes as the system configuration and parameters change, but a suitable method is not yet available. Existing approaches, such as proper orthogonal decomposition or machine learning are unsuitable because they require an inordinately large number of a priori simulations or experiments to generate a training dataset. We provide an alternative real-time temperature prediction tool which requires no a priori training for DC server enclosures into which a rack mountable cooling unit (RMCU) has been integrated. This new model is validated with experimental measurements and its applicability is demonstrated by separately evaluating the influence of varying IT server configuration, RMCU flowrate, step changes in system conditions, and interactions between multiple RMCUs. The resulting tool will facilitate advanced control techniques and optimize design for any DC rack-based cooling architecture. (C) 2018 Elsevier Ltd. All rights reserved.
引用
收藏
页码:890 / 900
页数:11
相关论文
共 40 条
[1]  
[Anonymous], 7 ACM SIGKDD INT C K
[2]  
[Anonymous], 130 SCHNEID EL
[3]   Surface-drag flow relations for zonal modeling [J].
Axley, JW .
BUILDING AND ENVIRONMENT, 2001, 36 (07) :843-850
[4]   Cooling systems in data centers: state of art and emerging technologies [J].
Capozzoli, Alfonso ;
Primiceri, Giulio .
SUSTAINABILITY IN ENERGY AND BUILDINGS: PROCEEDINGS OF THE 7TH INTERNATIONAL CONFERENCE SEB-15, 2015, 83 :484-493
[5]   Thermal metrics for data centers: a critical review [J].
Capozzoli, Alfonso ;
Serale, Gianluca ;
Liuzzo, Lucia ;
Chinnici, Marta .
6TH INTERNATIONAL CONFERENCE ON SUSTAINABILITY IN ENERGY AND BUILDINGS, 2014, 62 :391-400
[6]   A High-Fidelity Temperature Distribution Forecasting System for Data Centers [J].
Chen, Jinzhu ;
Tan, Rui ;
Wang, Yu ;
Xing, Guoliang ;
Wang, Xiaorui ;
Wang, Xiaodong ;
Punch, Bill ;
Colbry, Dirk .
PROCEEDINGS OF THE 2012 IEEE 33RD REAL-TIME SYSTEMS SYMPOSIUM (RTSS), 2012, :215-224
[7]   A simplified power consumption model of information technology (IT) equipment in data centers for energy system real-time dynamic simulation [J].
Cheung, Howard ;
Wang, Shengwei ;
Zhuang, Chaoqun ;
Gu, Jiefan .
APPLIED ENERGY, 2018, 222 :329-342
[8]   Evaluation of air distribution system's airflow performance for cooling energy savings in high-density data centers [J].
Cho, Jinkyun ;
Yang, Joonyoung ;
Park, Woopyoung .
ENERGY AND BUILDINGS, 2014, 68 :270-279
[9]   Economic analysis of data center cooling strategies [J].
Cho, Kyuman ;
Chang, Hyunjae ;
Jung, Yongho ;
Yoon, Yoojung .
SUSTAINABLE CITIES AND SOCIETY, 2017, 31 :234-243
[10]  
Dai J., 2014, Optimum Cooling of Data Centers