A Backup Protection Technique for Three-Terminal Multisection Compound Transmission Lines

被引:32
|
作者
Saber, Ahmed [1 ]
Emam, Ahmed [1 ]
Elghazaly, Hany [1 ]
机构
[1] Cairo Univ, Dept Elect Power & Machines, Giza 202, Egypt
关键词
Transmission lines; phasor measurement units; fault location; FAULT-LOCATION ALGORITHM; SYNCHRONIZED VOLTAGE; SCHEME;
D O I
10.1109/TSG.2017.2693322
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents a backup non-iterative protection technique for three-terminal multisection compound untransposed double-circuit transmission lines using synchronized phasor measurement units. The proposed technique is based on a distributed line model taking into account the mutual couplings between the two circuits. Synchronized voltage and current measurements in the phase domain are utilized for fault detection, classification, and location. The proposed technique can discriminate internal transmissions lines faults from other load change conditions or external faults and identify correctly the faulty branch and fault type, as well as determine accurately the fault location. The proposed algorithm is tested under different fault resistances, different fault locations, different fault inception angles, different fault types, non-linear high impedance faults, evolving faults, and synchrophasor errors, as well as transmission line parameters errors. Extensive simulation studies carried out using MATLAB software show that the proposed protection technique yields acceptable performance for all simulated cases.
引用
收藏
页码:5653 / 5663
页数:11
相关论文
共 50 条
  • [1] A Backup Protection Approach for Multisection Compound Transmission Lines
    Abdel-bary, A. S.
    Emam, A. M.
    Elghazaly, H. A.
    PROCEEDINGS OF 2016 EIGHTEENTH INTERNATIONAL MIDDLE EAST POWER SYSTEMS CONFERENCE (MEPCON), 2016, : 129 - 137
  • [2] An integrated backup protection and fault location module for unsynchronized three-terminal multisection hybrid transmission lines
    Anand, Shubham
    Kalita, Kaustav
    Parida, S. K.
    Bhalja, Bhavesh R.
    ELECTRIC POWER SYSTEMS RESEARCH, 2024, 233
  • [3] Fast & adaptive fault location technique for three-terminal lines
    Sardari, H.
    Mozafari, B.
    Shayanfar, H. A.
    ELECTRIC POWER SYSTEMS RESEARCH, 2020, 179
  • [4] An Algorithm for Locating Faults in Three-Terminal Multisection Nonhomogeneous Transmission Lines Using Synchrophasor Measurements
    Lin, Tzu-Chiao
    Lin, Pei-Yin
    Liu, Chih-Wen
    IEEE TRANSACTIONS ON SMART GRID, 2014, 5 (01) : 38 - 50
  • [5] Unsynchronised fault-location technique for three-terminal lines
    Mahamedi, Behnam
    Sanaye-Pasand, Majid
    Azizi, Sadegh
    Zhu, Jian Guo
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2015, 9 (15) : 2099 - 2107
  • [6] Phase Related Current Differential Protection of Three-terminal Transmission Lines
    Li, Bin
    Luo, Tao
    Bo, Zhiqian
    MATERIALS SCIENCE AND INFORMATION TECHNOLOGY, PTS 1-8, 2012, 433-440 : 5542 - +
  • [7] Unsynchronized fault-location technique for two- and three-terminal transmission lines
    Elsadd, Mahmoud A.
    Abdelaziz, Almoataz Y.
    ELECTRIC POWER SYSTEMS RESEARCH, 2018, 158 : 228 - 239
  • [8] A Fault Location Technique for Two-Terminal Multisection Compound Transmission Lines Using Synchronized Phasor Measurements
    Liu, Chih-Wen
    Lin, Tzu-Chiao
    Yu, Chi-Shan
    Yang, Jun-Zhe
    IEEE TRANSACTIONS ON SMART GRID, 2012, 3 (01) : 113 - 121
  • [9] A new technique, based on voltages, for fault location on three-terminal transmission lines
    Minambres, JF
    Zamora, I
    Mazon, AJ
    Zorrozua, MA
    AlvarezIsasi, R
    ELECTRIC POWER SYSTEMS RESEARCH, 1996, 37 (02) : 143 - 151
  • [10] PMU-based Fault Location Technique for Three-terminal Parallel Transmission Lines with Series Compensation
    Saber, Ahmed
    ELECTRIC POWER COMPONENTS AND SYSTEMS, 2020, 48 (4-5) : 410 - 422