Performance analysis of hybrid solid desiccant-vapor compression air conditioning system in hot and humid weather of India

被引:17
作者
Jani, D. B. [1 ]
Mishra, Manish [1 ]
Sahoo, P. K. [1 ]
机构
[1] Indian Inst Technol, Dept Mech & Ind Engn, Roorkee 247667, Uttar Pradesh, India
关键词
Dehumidifier effectiveness; coefficient of performance; hybrid desiccant cooling; regeneration temperature; Roorkee; PSYCHROMETRIC PROPERTIES; COOLING SYSTEM; DEHUMIDIFICATION; CLIMATES;
D O I
10.1177/0143624416633605
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
The performance of hybrid solid desiccant-vapor compression air conditioning system is studied for the typical hot and humid climatic zone of North India (Roorkee). The system consists of a rotary desiccant dehumidifier coupled with heat recovery wheel and a conventional vapor compression air conditioning system. A FORTRAN program was developed to calculate different psychrometric properties like humidity ratio, dry-bulb temperature, wet-bulb temperature, relative humidity, specific heat, etc. at each state point of the system on the basis of ambient and desired inside room conditions, room cooling load, sensible heat factor, and required air flow rate. The overall system performance has been evaluated in terms of the coefficient of performance and the dehumidifier effectiveness. The influence of variation in ambient conditions on regeneration temperature of desiccants has also been discussed. The simulated results are validated using experimental measurements. The present system has ensured a reduction of 79.15% in processing air humidity ratio at an outlet of the desiccant dehumidifier as compared to the outdoor humidity ratio. The results show that the performance of the system is significantly affected by the variations in ambient temperature and humidity ratio. Practical application: The proposed model of solid desiccant-VCR hybrid air conditioning system minimizes the energy usage in comfort cooling applications such as auditoriums, supermarket, hospitals, central library, offices, and lecture halls in hot and humid climate while maintaining an acceptable thermal comfort level and improving the performance. The proposed approach will give valuable insights to the researchers and building engineers to analyze the impacts of ambient conditions on the energy requirements and performance of solid desiccant cooling to ameliorate comfort, energy, and cost savings. Moreover, its potential contribution in environmental protection makes it more attractive at a time where depletion of energy resources and environmental degradation are of major concerns.
引用
收藏
页码:523 / 538
页数:16
相关论文
共 24 条
[11]   Analysis on a hybrid desiccant air-conditioning system [J].
Jia, C. X. ;
Dai, Y. J. ;
Wu, J. Y. ;
Wang, R. Z. .
APPLIED THERMAL ENGINEERING, 2006, 26 (17-18) :2393-2400
[12]  
Khamis KAA, 2000, THESIS
[13]  
Kiewkem T, 2013, ADV MAT RES, V622, P1575
[14]   Optimization of cooling load for a lecture theatre in a composite climate in India [J].
Kulkarni, K. ;
Sahoo, P. K. ;
Mishra, M. .
ENERGY AND BUILDINGS, 2011, 43 (07) :1573-1579
[15]   Case study and theoretical analysis of a solar driven two-stage rotary desiccant cooling system assisted by vapor compression air-conditioning [J].
La, Dong ;
Dai, Yanjun ;
Li, Yong ;
Ge, Tianshu ;
Wang, Ruzhu .
SOLAR ENERGY, 2011, 85 (11) :2997-3009
[16]   Performance assessment of hybrid desiccant cooling system at various climates [J].
Mandegari, Mohsen Ali ;
Pahlavanzadeh, Hassan .
ENERGY EFFICIENCY, 2010, 3 (03) :177-187
[17]  
Osman K, 2009, THESIS
[18]   Experimental analysis on performance of high temperature heat pump and desiccant wheel system [J].
Sheng, Ying ;
Zhang, Yufeng ;
Deng, Na ;
Fang, Lei ;
Nie, Jinzhe ;
Ma, Lijun .
ENERGY AND BUILDINGS, 2013, 66 :505-513
[19]   Numerical calculation of psychrometric properties on a calculator [J].
Singh, AK ;
Singh, H ;
Singh, SP ;
Sawhney, RL .
BUILDING AND ENVIRONMENT, 2002, 37 (04) :415-419
[20]   Parametric studies on a desiccant assisted air-conditioner [J].
Subramanyam, N ;
Maiya, MP ;
Murthy, SS .
APPLIED THERMAL ENGINEERING, 2004, 24 (17-18) :2679-2688