Automatic relative humidity optimization in underground heritage sites through ventilation system based on digital twins

被引:35
作者
Zhang, Jiaying [1 ]
Kwok, Helen H. L. [2 ]
Luo, Han [1 ]
Tong, Jimmy C. K. [3 ]
Cheng, Jack C. P. [1 ]
机构
[1] Hong Kong Univ Sci & Technol, Dept Civil & Environm Engn, Hong Kong 999077, Peoples R China
[2] Hong Kong Univ Sci & Technol, Inst Environm, Hong Kong 999077, Peoples R China
[3] Ove Arup & Partners Hong Kong Ltd, Hong Kong 999077, Peoples R China
关键词
HBIM; Underground heritage sites; Automatic ventilation system; Relative humidity; Digital twins; NUMERICAL-SIMULATION; DECENTRALIZED VENTILATION; PERFORMANCE PREDICTION; ENVIRONMENT; PRESSURE;
D O I
10.1016/j.buildenv.2022.108999
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Underground heritage sites generally experience significant humidity, which results in the destruction of the surfaces and structures. This study establishes an underground heritage site preservation mechanism through a dynamic ventilation system based on digital twin technology. The aim is to control the relative humidity (RH) gradually on the air region near the walls of sites within the standard range and reduce adverse physical equipment effects and energy consumption of the system. Underground heritage site projects have more complex shapes with irregular and nonlinear arcs and height difference distributions. It is challenging to regenerate them. To achieve this objective, a model simplification rule for irregular heritage building information modeling (HBIM) technology was first established via computational fluid dynamics (CFD) simulation. Second, a meth-odology was developed to design a reliable and effective ventilation equipment and its layout based on CFD for irregular heritage sites. Compared with the scheme based on the optimal geometric rule arrangement, the number of pipes can be reduced by up to 25%. Third, a web-based digital twin platform combined with Internet of Things (IoTs) technology was established for achieving real-time control of the overall RH level of under-ground heritage sites within the standard range. The results present new solutions to control the RH of under-ground heritage sites for preservation. The proposed methodology can be used in typical underground heritage sites and illustrated by a real case. The validation encompassed development of digital environment for the real case and development of the ventilation system for its RH optimization.
引用
收藏
页数:17
相关论文
共 54 条
  • [1] Development of the simulation model for Digital Twin applications in historical masonry buildings: The integration between numerical and experimental reality
    Angjeliu, Grigor
    Coronelli, Dario
    Cardani, Giuliana
    [J]. COMPUTERS & STRUCTURES, 2020, 238
  • [2] [Anonymous], 2022, AUTODESK REVIT HELP
  • [3] [Anonymous], 2018, ENV GUIDELINES AUSTR
  • [4] [Anonymous], WORLD HER LIST
  • [5] [Anonymous], 2016, C AUTODESK HELP
  • [6] Ansys ANSYS, 2013, FLUENT US GUID REL 1
  • [7] Cultural heritage protection via hybrid nanocomposite coating
    Azadi, Nasim
    Parsimehr, Hamidreza
    Ershad-Langroudi, Amir
    [J]. PLASTICS RUBBER AND COMPOSITES, 2020, 49 (09) : 414 - 424
  • [8] Barker A, 2011, LOW CARBON HERITAGE
  • [9] Blades N., 2000, GUIDELINES POLLUTION
  • [10] British Standards Institution, 2012, 54542012 BSI PD