A methodology for the performance evaluation of an experimental desiccant cooling system

被引:20
作者
Çarpinlioglu, MO
Yildirim, M
机构
[1] Univ Gaziantep, Fac Engn, Dept Mech Engn, TR-27310 Gaziantep, Turkey
[2] HVAC Ind, Gaziantep, Turkey
关键词
desiccant cooling system (DCS); desiccant wheel (DW); coefficient of performance (COP); cooling capacity (CC); regeneration temperature (T-R); system performance parameter (PP);
D O I
10.1016/j.icheatmasstransfer.2005.07.008
中图分类号
O414.1 [热力学];
学科分类号
摘要
An experimental investigation was conducted in an open cycle desiccant cooling system (DCS) operating on the ventilation mode in the laboratory site [M. Yildirim, An experimental investigation on heat and mass transfer in a desiccant cooling system, PhD thesis, Gaziantep University, Turkey (2002). [1]]. Although the operation of DCS is presumably affected by the design of primary components of rotary regenerator (RR) and desiccant wheel (DW) the methodology used in the analysis of experimental data is presented in this paper to set a different approach for the performance evaluation of similar systems. The rotational speeds of RR and DW (N-RR and N-DW), air mass flow rate (M-a) in process and regeneration lines, and the regeneration temperature (T-R) were defined as operation parameters. Meanwhile coefficient of performance (COP) and cooling capacity (CC) of the system were called as the performance parameters. The system operation with a variety of experimental conditions resulted in an extensive data set covering the ranges of N-RR, N-DW, m(a) and T-R as 5 rpm <= N-RR <= 20 rpm, 0.1 rpm <= N-DW <= 0.4 rpm, 0.05 kg/s <= m(a)0.139 kg/s and 60 degrees C <= T-R <= 90 degrees C, respectively. The interactive influence of the operation parameters was determined through the realization of the psychrometric cycle in deviation from an ideal cycle. A dimensional analysis based on a trial and error procedure was followed to determine the functional relationship of COP and CC. The proposed correlations between COP and CC and the introduced system performance parameter (PP) were determined to be a sole function of m(a) independent of N-RR, N-DW and T-R in their covered ranges. (c) 2005 Elsevier Ltd. All rights reserved.
引用
收藏
页码:1400 / 1410
页数:11
相关论文
共 29 条
  • [1] Desiccant aging and its effects on desiccant cooling system performance
    Belding, WA
    Delmas, MPF
    Holeman, WD
    [J]. APPLIED THERMAL ENGINEERING, 1996, 16 (05) : 447 - 459
  • [2] BORDE I, 1991, STUDIES AIR DRYING 2, P207
  • [3] *BRIT STAND I, 1964, 1042 BRIT STAND I 1
  • [4] Cengel YA., 1998, HEAT TRANSFER PRACTI
  • [5] Study of a solar powered solid adsorption-desiccant cooling system used for grain storage
    Dai, YJ
    Wang, RZ
    Xu, YX
    [J]. RENEWABLE ENERGY, 2002, 25 (03) : 417 - 430
  • [6] The use of solar desiccant cooling in the UK: a feasibility study
    Halliday, SP
    Beggs, CB
    Sleigh, PA
    [J]. APPLIED THERMAL ENGINEERING, 2002, 22 (12) : 1327 - 1338
  • [7] The potential of solar energy use in desiccant cooling cycles
    Henning, HM
    Erpenbeck, T
    Hindenburg, C
    Santamaria, IS
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2001, 24 (03): : 220 - 229
  • [8] HICKMAN MJ, 1970, MEASUREMENT HUMIDITY
  • [9] JALALZADEHAZAR AA, 2000, ASHRAE T, V106, P210
  • [10] JALAZADEHAZAR AA, 1978, SOL ENERGY, V21, P273